Plan Review Notes
Plan Review Notes For Permit 09090423
Permit Number 09090423
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-25 10:22:28 
 ** DENIED PLANS **
  
  
  
 1) NOTE: AS OF DECEMBER 31ST, 2008. THE CURRENT EDITION
 OF NFPA- 101 IS THE 2006. THE PLANS STATE 2003. PLEASE
 ADJUST.
  
 2) NOTE: THERE IS A NEED FOR PLANS TO COORDINATE FOR
 SERVICE. ARCHITECTURAL PLANS INDICATE THAT EXISTING
 PANELS AND DISCONNECT ARE LOCATED INSIDE TO BE REMOVED.
 HOWEVER THE ELECTRICAL RISER INDICATES THE MAIN
 DISCONNECT AS EXISTING AND IT BEING LOCATED OUTSIDE.
 PLEASE SHOW LOCATION AND COORDINATE PLANS AS TO WHETHER
 OR NOT SERVICE IS NEW AND LOCATION.
 PLEASE SEE NEC 110.26, 230.70, 230.71, 110.9 ETC
 AS PLANS INDICATE ALL SERVICE EQUIPMENT AND MAIN BEING
 REMOVED PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM, AIC
 RATING OF MAIN AND SIZE OF THE NEW CONDUCTORS.
  
 3) NOTE: PLEASE SEE E-1 AS THE PLANS INDICATE THERE IS
 PANELS *B* AND *C*, YET RISER STATES PANELS A AND B.
 PLEASE ALSO SEE THAT THE PANEL *A* STATES A 2-POLE
 60AMP BREAKER FEEDING PANEL *B* HOWEVER PANEL *B* LOAD
 EXCEEDS THE RATING OF THIS BREAKER. THE LOAD IS SHOWN
 AT 72AMPS YET ONLY A 60AMP BREAKER IS SHOWN.
 215.5, 240.4, 230, 310.16,408 ETC
  
 4) NOTE:
  
 A) PLEASE COORDINATE RISER AND PANELS. PANEL *A*
 INDICATES #6 AWG FOR THE SAME 60AMP BREAKER FEEDING
 PANEL *B* YET THE RISER INDICATES #3 CONDUCTORS?? AS
 NOTED ABOVE IN COMMENT #3, THE #6 IS NOT RATED FOR LOAD
 OF PANEL *B* AS SHOWN. 310.16,240.4
  
 B) PLEASE COORDINATE THE PANEL INFORMATION FOR PANEL
 *B*. PANEL *B* STATES IT WILL BE A 42POLE 125AMP PANEL,
 YET THE PANEL IS SHOWN AS A 30 CIRCUIT/POLE PANEL.
 NEC 408, 230
  
 5) NOTE: THE SPACE BY SPACE LIGHTING ALLOWANCES DO NOT
 MEET 13-415.AB.5, 13-415.B.1. IT IS NOT PERMISSIBLE TO
 USE RETAIL FOR OTHER AREAS SUCH AS WALK IN COOLER AREA,
 BATHROOM ETC. THESE NEED TO BE SEPARATE TO SPACE BY
 SPACE.
 ** ALSO NO FIXTURE LEGEND SUBMITTED FOR ENOUGH
 INFORMATION ON LIGHTING FIXTURES FOR A COMPLETE REVIEW
 FOR CODE COMPLIANCE.
  
 6) NOTE: NO EXTERIOR LIGHTING CALCULATIONS SUBMITTED.
 13-415.AB.2.2.
  
 7) NOTE: NO EXTERIOR LIGHTING CONTROLS PER
 13-415.AB.1.4 SHOWN. MUST MEET AT LEAST ONE OF THE TWO
 METHODS REQUIRED. THE TC AS SHOWN ON RISER DOES NOT
 PROVIDE ANY INFORMATION FOR ITS USE OR THE TYPE AS
 REQUIRED IN SECTION ABOVE. A STANDARD SINGLE POLE TIME
 CLOCK DOES NOT MEET FBC SECTION GIVEN.
 ** THE PLANS ALSO INDICATE THE SPRINKLER PUMP TO BE ON
 TIME CLOCK. AS ONLY ONE IS SHOWN ON RISER IT IS BEING
 ASSUMED THE TC IS FOR THE SPRINKLER PUMP. SEE COMMENTS
 BELOW ABOUT THE PUMP.
  
 8) NOTE: THE WALK-IN GLASS DOOR COOLER AREA DOES NOT
 INDICATE ANY LIGHTING OR LIGHTING CONTROLS. IS THERE
 NOT GOING TO BE ANY LIGHTS IN THIS AREA? THE PANEL
 SCHEDULE INDICATES A CIRCUIT FOR WALK IN LIGHTS AND
 HEATER HOWEVER NO INFORMATION ON PLANS.
 NFPA-101 7.8
 ** PLEASE ALSO KEEP IN MIND, FBC
 13-415.AB.1.1,.1.2,.1.3 ALL APPLY TO COOLER WALK IN
 LIGHTS.
  
 9) NOTE: ** PLEASE COORDINATE ALL PLANS AND REQUIRED
 CIRCUITING/LOADS.
  
 A) THE WP GFI SHOWN ON THE MECHANICAL PLANS INDICATES
 THIS RECEPTACLE BEING CIRCUITED TO A-4. HOW IS THIS
 POSSIBLE WHEN A2,4 IS THE SAME CIRCUIT FOR CONDENSING
 UNIT?
 PLEASE SEE 210.63, 210.8B
  
 B) PLEASE SEE M SHEETS AS THE WIC EVAPORATOR CIRCUIT IS
 SHOWN AS 18/20, HOWEVER PER PANEL *A* SCHEDULE 18 IS
 PART OF THE AHU-2 CIRCUIT AND 20/22 IS THE WIC CIRCUIT.
  
 C) PLEASE SEE POWER PLANS. WHERE IS THE ELECTRICAL FOR
 THE WIC UNIT INSIDE THE COOLER? A J-BOX SYMBOL IS SHOWN
 ON PLANS, HOWEVER NO CIRCUIT, NO DISCONNECT ETC IS
 SHOWN.
  
 10) NOTE: WHEN FIGURING SHOW WINDOW LOAD FOR SERVICE
 220.43A MUST BE USED AND FIGURED. ONLY 220.14G MAY BE
 USED FOR BRANCH CIRCUIT WHEN NOT USING 200 VA PER FT.
  
 11) NOTE: PLEASE SEE NEC 422.13 AS STORAGE TYPE WATER
 HEATERS ARE REQUIRED TO HAVE LOADS FIGURED AT 125%.
 THIS WAS A CHANGE IN THE 2005 NEC IN WHICH THESE TYPES
 OF WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD.
 PLEASE SEE THE LAST LINE IN THE COMMENTARY SECTION OF
 422.13 IN THE NEC HANDBOOK.
  
 12) NOTE: THE PLANS INDICATE THERE IS GOING TO BE A
 SPRINKLER PUMP AND IT WILL BE ON THE TIME CLOCK.
 HOWEVER THE LOAD SHOWN FOR TIME CLOCK IS 180VA. THIS IS
 NOT POSSIBLE FOR AN IRRIGATION PUMP. THIS IS SHOWN AS
 SINGLE PHASE PUMP, PER NEC 430.248, EVEN THE SMALLEST
 115V PUMP AS 1/6TH HP HAS A VA MUCH HIGHER THAN 180VA.
 WHERE IS THE PUMP GOING TO BE LOCATED? THE PLANS
 INDICATE THE RECEPTACLE IN THE FRONT OF THE STORE ALONG
 AN INSIDE COUNTER.
 THE LANDSCAPE PLANS DO NOT DETAIL PUMP LOCATION.
  
 ** AS THERE IS INFORMATION NOT YET COMPLETE OR SHOWN ON
 PLANS, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  