2009-09-25 10:22:28 | |
| ** DENIED PLANS ** |
| |
| |
| |
| 1) NOTE: AS OF DECEMBER 31ST, 2008. THE CURRENT EDITION |
| OF NFPA- 101 IS THE 2006. THE PLANS STATE 2003. PLEASE |
| ADJUST. |
| |
| 2) NOTE: THERE IS A NEED FOR PLANS TO COORDINATE FOR |
| SERVICE. ARCHITECTURAL PLANS INDICATE THAT EXISTING |
| PANELS AND DISCONNECT ARE LOCATED INSIDE TO BE REMOVED. |
| HOWEVER THE ELECTRICAL RISER INDICATES THE MAIN |
| DISCONNECT AS EXISTING AND IT BEING LOCATED OUTSIDE. |
| PLEASE SHOW LOCATION AND COORDINATE PLANS AS TO WHETHER |
| OR NOT SERVICE IS NEW AND LOCATION. |
| PLEASE SEE NEC 110.26, 230.70, 230.71, 110.9 ETC |
| AS PLANS INDICATE ALL SERVICE EQUIPMENT AND MAIN BEING |
| REMOVED PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM, AIC |
| RATING OF MAIN AND SIZE OF THE NEW CONDUCTORS. |
| |
| 3) NOTE: PLEASE SEE E-1 AS THE PLANS INDICATE THERE IS |
| PANELS *B* AND *C*, YET RISER STATES PANELS A AND B. |
| PLEASE ALSO SEE THAT THE PANEL *A* STATES A 2-POLE |
| 60AMP BREAKER FEEDING PANEL *B* HOWEVER PANEL *B* LOAD |
| EXCEEDS THE RATING OF THIS BREAKER. THE LOAD IS SHOWN |
| AT 72AMPS YET ONLY A 60AMP BREAKER IS SHOWN. |
| 215.5, 240.4, 230, 310.16,408 ETC |
| |
| 4) NOTE: |
| |
| A) PLEASE COORDINATE RISER AND PANELS. PANEL *A* |
| INDICATES #6 AWG FOR THE SAME 60AMP BREAKER FEEDING |
| PANEL *B* YET THE RISER INDICATES #3 CONDUCTORS?? AS |
| NOTED ABOVE IN COMMENT #3, THE #6 IS NOT RATED FOR LOAD |
| OF PANEL *B* AS SHOWN. 310.16,240.4 |
| |
| B) PLEASE COORDINATE THE PANEL INFORMATION FOR PANEL |
| *B*. PANEL *B* STATES IT WILL BE A 42POLE 125AMP PANEL, |
| YET THE PANEL IS SHOWN AS A 30 CIRCUIT/POLE PANEL. |
| NEC 408, 230 |
| |
| 5) NOTE: THE SPACE BY SPACE LIGHTING ALLOWANCES DO NOT |
| MEET 13-415.AB.5, 13-415.B.1. IT IS NOT PERMISSIBLE TO |
| USE RETAIL FOR OTHER AREAS SUCH AS WALK IN COOLER AREA, |
| BATHROOM ETC. THESE NEED TO BE SEPARATE TO SPACE BY |
| SPACE. |
| ** ALSO NO FIXTURE LEGEND SUBMITTED FOR ENOUGH |
| INFORMATION ON LIGHTING FIXTURES FOR A COMPLETE REVIEW |
| FOR CODE COMPLIANCE. |
| |
| 6) NOTE: NO EXTERIOR LIGHTING CALCULATIONS SUBMITTED. |
| 13-415.AB.2.2. |
| |
| 7) NOTE: NO EXTERIOR LIGHTING CONTROLS PER |
| 13-415.AB.1.4 SHOWN. MUST MEET AT LEAST ONE OF THE TWO |
| METHODS REQUIRED. THE TC AS SHOWN ON RISER DOES NOT |
| PROVIDE ANY INFORMATION FOR ITS USE OR THE TYPE AS |
| REQUIRED IN SECTION ABOVE. A STANDARD SINGLE POLE TIME |
| CLOCK DOES NOT MEET FBC SECTION GIVEN. |
| ** THE PLANS ALSO INDICATE THE SPRINKLER PUMP TO BE ON |
| TIME CLOCK. AS ONLY ONE IS SHOWN ON RISER IT IS BEING |
| ASSUMED THE TC IS FOR THE SPRINKLER PUMP. SEE COMMENTS |
| BELOW ABOUT THE PUMP. |
| |
| 8) NOTE: THE WALK-IN GLASS DOOR COOLER AREA DOES NOT |
| INDICATE ANY LIGHTING OR LIGHTING CONTROLS. IS THERE |
| NOT GOING TO BE ANY LIGHTS IN THIS AREA? THE PANEL |
| SCHEDULE INDICATES A CIRCUIT FOR WALK IN LIGHTS AND |
| HEATER HOWEVER NO INFORMATION ON PLANS. |
| NFPA-101 7.8 |
| ** PLEASE ALSO KEEP IN MIND, FBC |
| 13-415.AB.1.1,.1.2,.1.3 ALL APPLY TO COOLER WALK IN |
| LIGHTS. |
| |
| 9) NOTE: ** PLEASE COORDINATE ALL PLANS AND REQUIRED |
| CIRCUITING/LOADS. |
| |
| A) THE WP GFI SHOWN ON THE MECHANICAL PLANS INDICATES |
| THIS RECEPTACLE BEING CIRCUITED TO A-4. HOW IS THIS |
| POSSIBLE WHEN A2,4 IS THE SAME CIRCUIT FOR CONDENSING |
| UNIT? |
| PLEASE SEE 210.63, 210.8B |
| |
| B) PLEASE SEE M SHEETS AS THE WIC EVAPORATOR CIRCUIT IS |
| SHOWN AS 18/20, HOWEVER PER PANEL *A* SCHEDULE 18 IS |
| PART OF THE AHU-2 CIRCUIT AND 20/22 IS THE WIC CIRCUIT. |
| |
| C) PLEASE SEE POWER PLANS. WHERE IS THE ELECTRICAL FOR |
| THE WIC UNIT INSIDE THE COOLER? A J-BOX SYMBOL IS SHOWN |
| ON PLANS, HOWEVER NO CIRCUIT, NO DISCONNECT ETC IS |
| SHOWN. |
| |
| 10) NOTE: WHEN FIGURING SHOW WINDOW LOAD FOR SERVICE |
| 220.43A MUST BE USED AND FIGURED. ONLY 220.14G MAY BE |
| USED FOR BRANCH CIRCUIT WHEN NOT USING 200 VA PER FT. |
| |
| 11) NOTE: PLEASE SEE NEC 422.13 AS STORAGE TYPE WATER |
| HEATERS ARE REQUIRED TO HAVE LOADS FIGURED AT 125%. |
| THIS WAS A CHANGE IN THE 2005 NEC IN WHICH THESE TYPES |
| OF WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD. |
| PLEASE SEE THE LAST LINE IN THE COMMENTARY SECTION OF |
| 422.13 IN THE NEC HANDBOOK. |
| |
| 12) NOTE: THE PLANS INDICATE THERE IS GOING TO BE A |
| SPRINKLER PUMP AND IT WILL BE ON THE TIME CLOCK. |
| HOWEVER THE LOAD SHOWN FOR TIME CLOCK IS 180VA. THIS IS |
| NOT POSSIBLE FOR AN IRRIGATION PUMP. THIS IS SHOWN AS |
| SINGLE PHASE PUMP, PER NEC 430.248, EVEN THE SMALLEST |
| 115V PUMP AS 1/6TH HP HAS A VA MUCH HIGHER THAN 180VA. |
| WHERE IS THE PUMP GOING TO BE LOCATED? THE PLANS |
| INDICATE THE RECEPTACLE IN THE FRONT OF THE STORE ALONG |
| AN INSIDE COUNTER. |
| THE LANDSCAPE PLANS DO NOT DETAIL PUMP LOCATION. |
| |
| ** AS THERE IS INFORMATION NOT YET COMPLETE OR SHOWN ON |
| PLANS, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| |
| |
| ** IMPORTANT** |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |