2009-10-09 19:12:04 | |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE SEE FAC 69A-3.012 AS THE NFPA-30 NOTED |
| ON PLANS SHOULD BE THE 2003 EDITION. PLEASE SEE FBC |
| 2007 W/2009 REVISIONS ALONG WITH FAC 69A-3.012 ETC AS |
| THE CURRENT EDITION OF THE NEC IS THE 2005 EDITION. ALL |
| PERMIT APPLICATIONS AFTER DECEMBER 8TH, 2006 AND UP TOT |
| OCT 1ST 2009 ARE UNDER THE 2005 NFPA-70. |
| STATING LATEST EDITION ON PLANS IS NOT PERMITTED AS THE |
| LATEST EDITION COULD PLACE PROJECT INTO ANOTHER CODE. |
| |
| 2) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS |
| ON PLANS AND WIRING METHODS PER NEC 514.3. PLEASE SEE |
| THE NEC HANDBOOK AS SEVERAL FIGURES AND DETAILS ARE |
| PROVIDED FOR REFERENCE AND MINIMUMS. |
| PLEASE SHOW TYPICAL DETAILS FOR SEAL-OFFS AND WIRING |
| METHOD DETAILS. 514.8 |
| PLEASE SHOW LOCATION OF NEW OR EXISTING EMERGENCY |
| DISCONNECTS PER 514.11A, B AND C. |
| **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| 3) NOTE: CONDUCTORS, OVER CURRENT PROTECTION SIZES |
| COORDINATING WITH PUMP DETAILS NEEDS TO BE ON PLANS. |
| PLEASE SEE 310.16,240.4 AND 408.4 FOR PANEL SCHEDULE. |
| |
| ** FBC ADMINISTRATIVE SECTION FRO ADDITIONAL |
| INFORMATION ON PLANS TO SHOW MINIMUM CODE COMPLIANCE. |
| 106.1.1,106.1.2, 106.3.5.1.2 AS ADOPTED BY THE CITY OF |
| WEST PALM BEACH |
| |
| |
| |
| |
| **IMPORTANT** |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |