Plan Review Notes
Plan Review Notes For Permit 09090397
Permit Number 09090397
Review Stop B
Sequence Number 1
Notes
Date Text
2009-09-17 17:05:01RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NOA 03-0501.02 FOR WOOD DECKS AND NOA 03-0501.03 FOR
 LWC DECKS SUBMITTED ARE EXPIRED. NEED TO PROVIDE
 CURRENT NOA'S.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 ***NOTE: IF GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED REQUIRE SIGNED AND SEALED RAS 117
 CALCULATIONS, THEN PROVIDE ORIGINAL SIGNED AND SEALED
 CALCULATIONS.
 ALSO, DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 VERIFY IF BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC.
 1609..4.3 OF 2009 REVISIONS TO THE 2007 FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved