2009-10-17 09:47:35 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGE 5 SHOWS TWO FLEX DUCTS PENETRATING THE ONE HOUR |
| STAIR ENCLOSURE. FLEXIBLE DUCTS SHALL NOT PASS THROUGH |
| ANY FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH |
| FBC-M 607.7. ALSO, PENETRATIONS INTO AND OPENINGS |
| THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR |
| REQUIRED EXIT DOORS IN ACCORDANCE WITH FBC-B 1020.1.2. |
| AN INDEPENDENT SYSTEM IS REQUIRED IF VENTILATION IS TO |
| BE PROVIDED IN THE STAIR ENCLOSRE IN ACCORDANCE WITH |
| FBC-B 1020.1.3. |
| |
| 2. SHOW CFM QUANTITY FOR 1ST FLOOR BATHROOM EXHAUST |
| FANS IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEANS |
| AND LOCATION OF EXHAUST DISCHARGE IN ACCORDANCE WITH |
| FBC-M 401.4 AND 401.5. |
| |
| 3. SHOW MEANS AND LOCATION OF CONDENSATE DISCHARGE FOR |
| 1ST AND 2ND FLOOR AC UNITS IN ACCORDANCE WITH FBC-M |
| 307.2.1. |
| NOTE: PVC IS A COMBUSTIBLE MATERIAL AND SHALL NOT BE |
| USED IN THE 2ND FLOOR RETURN AIR PLENUM CLOSET IN |
| ACCORDANCE WITH FBC-M 602.2.1. |
| |
| 4. PROVIDE MANUFACTURER'S DATA FOR THE PTAC UNITS ON |
| FIRST FLOOR SHOWING THESE APPLIANCE ARE DESIGNED FOR |
| WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. ALSO |
| PROVIDE AN ENGINEERED WIND RESISTANT INSTALLATION |
| DETAIL FOR THE PTAC SLEEVE AS WELL AS FOR THE |
| ATTACHMENT OF THE UNIT WITHIN THE SLEEVE. |
| |
| NOTE: CODE TABULATION INDICATES THIS PROJECT IS SUBJECT |
| TO THE 2007 FLORIDA BUILDING CODE, RESIDENTIAL. THIS IS |
| A MULTI-FAMILY BUILDING AND IS THEREFORE BEING REVIEWED |
| FOR COMPLIANCE WITH THE REQUIREMENTS OF THE 2007 |
| FLORIDA BUILDING CODE, MECHANICAL AS WELL AS SECTION |
| 13-600 OF THE FLORIDA BUILDING CODE, BUILDING AND THE |
| FLORIDA BUILDING CODE, EXISTING BUILDING. |
| |