Plan Review Notes
Plan Review Notes For Permit 09090386
Permit Number 09090386
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-19 15:48:07*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. SHOW THE LOCATION OF THE PORTABLE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 4. SMOKE ALARMS, NOT SMOKE DETECTORS, SHALL BE
 INSTALLED. PLEASE BE ADVISED THAT SMOKE DETECTORS ARE
 TIED INTO A BUILDING'S FIRE ALARM SYSTEM, WHEREAS,
 SMOKE ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL
 DWELLING UNIT , SUITE OF ROOMS, OR SIMILIAR AREA.
  
 5. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 HAVE NOT LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
  
 6. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 SELF CLOSING AND SELF LATCHING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722