2009-09-26 12:01:27 | |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLANS NEED TO CONTAIN THE FOLLOWING ADOPTED |
| RELEVANT CODES FOR DESIGN. |
| 2005 NFPA-70 ( NEC) |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLANS INDICATE AN EQUIPMENT GROUNDING |
| CONDUCTORS BEFORE THE FIRST MEANS OF DISCONNECT WHICH |
| IS NOT PERMITTED. |
| 250.24, 250.6 |
| |
| 3) NOTE: PLANS DO NOT SHOW DISCONNECTING MEANS FOR THE |
| CU. 440.11,440.12 |
| |
| 4) NOTE: PLANS SHOW SMOKE DETECTORS HOWEVER THESE SEEM |
| THEY SHOULD BE SMOKE ALARMS. SMOKE DETECTORS ARE |
| DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN ALARM. IF |
| THESE ARE ACTUALLY SMOKE DETECTORS THEN PLEASE SHOW |
| LOCATIONS OF SOUNDING DEVICES/ALARMS. IF THESE ARE |
| INDEED SMOKE ALARMS PLEASE ADJUST PLANS. |
| NFPA-72 11.5.1, 11.8.3, R313.2.1 |
| ** SEE DEVICES LOCATED WITHIN 20FT OF COOKING |
| APPLIANCES. |
| |
| 5) NOTE: STAIR SWITCHES SHOULD BE INDICATED AS 3-WAY |
| TYPE DEVICES. ALSO REAR STAIRS NEED TO HAVE A CONTROL |
| AT BOTTOM OF STAIRS. |
| 210.70 |
| |
| 6) NOTE: PLEASE SEE 250.66 AS THE GROUNDING ELECTRODE |
| CONDUCTOR IS SHOWN AS A #2 CONDUCTOR WHEN PER 250.66 IT |
| IS REQUIRED TO BE LARGER. THIS GOES WITH COMMENT #2 |
| ABOVE. |
| ** PLEASE CALL TO GO OVER. |
| |
| 7) NOTE: THE RISER SEEMS TO INDICATE A 400AMP MAIN |
| BEFORE METER BANK HOWEVER THIS IS NOT CLEAR. PLEASE |
| VERIFY WITH FPL THE DISCONNECTING MEANS AHEAD OF |
| METERING DEVICES. |
| RISER SHOWS METERS AFTER SERVICE DISCONNECTING MEANS |
| HOWEVER NO CT AHEAD OF MAIN. |
| SEE 2009 FPL SERVICE STANDARDS. |
| |
| 8) NOTE: AS ROOMS/AREAS ARE NOT IDENTIFIED ON PLANS THE |
| FOLLOWING WILL BE NOTED AS BEST POSSIBLE. |
| PLEASE SEE 210.52 AS THERE ARE SOME RECEPTACLE |
| REQUIRED. SEE LEVEL 1 MAIN ENTRANCE FOR BOTH UNITS |
| WHICH REQUIRES RECEPTACLE WITHIN 6FT OF DOOR. |
| ALSO WALLS WITH MORE THAN 12FT WHICH REQUIRE ADDITIONAL |
| DEVICES. |
| SECOND LEVEL AT REAR WALL. |
| |
| 9) NOTE: PLEASE SEE FBC 108.3. SCOPE OF WORK NEEDS TO |
| INLCUDE ALL LABOR, MATERIALS, EQUIPMENT ETC FOR ALL |
| TRADES INCLUDING DESIGN FEES EVEN IF ANY OF THESE ITEMS |
| ARE OWNER SUPPLIED. AS ALL SUB CONTRACTORS ARE SIGNED |
| ON, VALUE FOR ALL TRADES NEED TO BE INCLUDED. |
| |
| |
| |
| IMPORTANT** |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |