Plan Review Notes
Plan Review Notes For Permit 09090386
Permit Number 09090386
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-26 12:01:27 
  
 ** DENIED **
  
 1) NOTE: PLANS NEED TO CONTAIN THE FOLLOWING ADOPTED
 RELEVANT CODES FOR DESIGN.
 2005 NFPA-70 ( NEC)
 2002 NFPA-72
  
 2) NOTE: PLANS INDICATE AN EQUIPMENT GROUNDING
 CONDUCTORS BEFORE THE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED.
 250.24, 250.6
  
 3) NOTE: PLANS DO NOT SHOW DISCONNECTING MEANS FOR THE
 CU. 440.11,440.12
  
 4) NOTE: PLANS SHOW SMOKE DETECTORS HOWEVER THESE SEEM
 THEY SHOULD BE SMOKE ALARMS. SMOKE DETECTORS ARE
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN ALARM. IF
 THESE ARE ACTUALLY SMOKE DETECTORS THEN PLEASE SHOW
 LOCATIONS OF SOUNDING DEVICES/ALARMS. IF THESE ARE
 INDEED SMOKE ALARMS PLEASE ADJUST PLANS.
 NFPA-72 11.5.1, 11.8.3, R313.2.1
 ** SEE DEVICES LOCATED WITHIN 20FT OF COOKING
 APPLIANCES.
  
 5) NOTE: STAIR SWITCHES SHOULD BE INDICATED AS 3-WAY
 TYPE DEVICES. ALSO REAR STAIRS NEED TO HAVE A CONTROL
 AT BOTTOM OF STAIRS.
 210.70
  
 6) NOTE: PLEASE SEE 250.66 AS THE GROUNDING ELECTRODE
 CONDUCTOR IS SHOWN AS A #2 CONDUCTOR WHEN PER 250.66 IT
 IS REQUIRED TO BE LARGER. THIS GOES WITH COMMENT #2
 ABOVE.
 ** PLEASE CALL TO GO OVER.
  
 7) NOTE: THE RISER SEEMS TO INDICATE A 400AMP MAIN
 BEFORE METER BANK HOWEVER THIS IS NOT CLEAR. PLEASE
 VERIFY WITH FPL THE DISCONNECTING MEANS AHEAD OF
 METERING DEVICES.
 RISER SHOWS METERS AFTER SERVICE DISCONNECTING MEANS
 HOWEVER NO CT AHEAD OF MAIN.
 SEE 2009 FPL SERVICE STANDARDS.
  
 8) NOTE: AS ROOMS/AREAS ARE NOT IDENTIFIED ON PLANS THE
 FOLLOWING WILL BE NOTED AS BEST POSSIBLE.
 PLEASE SEE 210.52 AS THERE ARE SOME RECEPTACLE
 REQUIRED. SEE LEVEL 1 MAIN ENTRANCE FOR BOTH UNITS
 WHICH REQUIRES RECEPTACLE WITHIN 6FT OF DOOR.
 ALSO WALLS WITH MORE THAN 12FT WHICH REQUIRE ADDITIONAL
 DEVICES.
 SECOND LEVEL AT REAR WALL.
  
 9) NOTE: PLEASE SEE FBC 108.3. SCOPE OF WORK NEEDS TO
 INLCUDE ALL LABOR, MATERIALS, EQUIPMENT ETC FOR ALL
 TRADES INCLUDING DESIGN FEES EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED. AS ALL SUB CONTRACTORS ARE SIGNED
 ON, VALUE FOR ALL TRADES NEED TO BE INCLUDED.
  
  
  
 IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717