Plan Review Notes
Plan Review Notes For Permit 09090357
Permit Number 09090357
Review Stop P
Sequence Number 2
Notes
Date Text
2009-10-22 09:48:31DENIED
 REFERENCE:
 FBC-2007 PLUMIBNG
 FBC-2007 EXISTING BLDG
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-3 BATHROOM 204 SHALL BE ADAPTABLE. PLEASE SHOW
 COMPLIANCE WITH THE W/C 18" FROM THE CENTERLINE OF THE
 FIXTURE TO THE WALL. FIGURE 28. - BACKING FOR THE W/C
 AND THE SHOWER. SECTIONS 11-4.16.4 & 11-4.21.4 AS WELL
 AS FIGURES 29 & 37. SHOWER CONTROLS. SECTION 11-4.21.5
 & FIGURE 37. THE CURB. SECTION 11-4.21.7. AND THE
 TURNING AREA PER SECTION 11-4.23.3.
 ****RESPONSE NOTED, BUT SINCE UNITS WERE ORIGINALLY
 INDICATED AS R-2 OCCUPANCY AND IS NOW A B OCCUPANCY
 THIS IS A CHANGE OF OCCUPANCY. PER SECTION 906.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING. SEE
 SECTION 11-4.1.3(11). TO BE ADAPTABLE THE BACKING FOR
 THE GRAB BARS SHALL BE INSTALLED, THE W/C SHALL BE 18"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, THE
 TURNING AREA SHALL BE INDICATED, THE VALVE LOCATION FOR
 THE SHOWER SHALL BE INDICATED AND THE CURB FOR THE
 SHOWER IS NOT APPROVED.
  
 2. SHT A-3 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN IS
 INDICATED IN THE COMMON AREA. SUBMIT PLANS SHOWING THE
 LOCATION OF THE EXISTING DRINKING FOUNTAIN.
  
 3. SHT P-1 NO WATER PIPING/SANITARY PIPING SHOWN FOR
 THE REQUIRED DRINKING FOUNTAIN. PLEASE SUBMIT ISOMETRIC
 RISER DIAGRAMS FOR BOTH AS WELL AS INDICATING THE
 LOCATION OF THE PIPING ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(1)(3)(4)(6)(10)(13).
 ****RESPONSE NOTED, WHEN COMMENT NUMBER 2 IS ADDRESSED
 SHOWING THE CLEAR FLOOR SPACE FOR THE EXISTING DRINKING
 FOUNTAIN THEN COMMENT WILL BE ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved