Plan Review Notes
Plan Review Notes For Permit 09090357
Permit Number 09090357
Review Stop P
Sequence Number 1
Notes
Date Text
2009-09-22 07:59:21DENIED
 REFERENCE:
 FBC-2007 PLUMIBNG
 FBC-2007 EXISTING BLDG
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-3 BATHROOM 204 SHALL BE ADAPTABLE. PLEASE SHOW
 COMPLIANCE WITH THE W/C 18" FROM THE CENTERLINE OF THE
 FIXTURE TO THE WALL. FIGURE 28. - BACKING FOR THE W/C
 AND THE SHOWER. SECTIONS 11-4.16.4 & 11-4.21.4 AS WELL
 AS FIGURES 29 & 37. SHOWER CONTROLS. SECTION 11-4.21.5
 & FIGURE 37. THE CURB. SECTION 11-4.21.7. AND THE
 TURNING AREA PER SECTION 11-4.23.3.
  
 2. SHT A-3 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 3. SHT P-1 NO WATER PIPING/SANITARY PIPING SHOWN FOR
 THE REQUIRED DRINKING FOUNTAIN. PLEASE SUBMIT ISOMETRIC
 RISER DIAGRAMS FOR BOTH AS WELL AS INDICATING THE
 LOCATION OF THE PIPING ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(1)(3)(4)(6)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  