2009-09-22 07:59:21 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMIBNG |
| FBC-2007 EXISTING BLDG |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| |
| 1. SHT A-3 BATHROOM 204 SHALL BE ADAPTABLE. PLEASE SHOW |
| COMPLIANCE WITH THE W/C 18" FROM THE CENTERLINE OF THE |
| FIXTURE TO THE WALL. FIGURE 28. - BACKING FOR THE W/C |
| AND THE SHOWER. SECTIONS 11-4.16.4 & 11-4.21.4 AS WELL |
| AS FIGURES 29 & 37. SHOWER CONTROLS. SECTION 11-4.21.5 |
| & FIGURE 37. THE CURB. SECTION 11-4.21.7. AND THE |
| TURNING AREA PER SECTION 11-4.23.3. |
| |
| 2. SHT A-3 A DRINKING FOUNTAIN IS REQUIRED PER TABLE |
| 403.1. PLEASE SHOW THE LOCATION OF THE DRINKING |
| FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| |
| 3. SHT P-1 NO WATER PIPING/SANITARY PIPING SHOWN FOR |
| THE REQUIRED DRINKING FOUNTAIN. PLEASE SUBMIT ISOMETRIC |
| RISER DIAGRAMS FOR BOTH AS WELL AS INDICATING THE |
| LOCATION OF THE PIPING ON THE FLOOR PLAN. SECTION |
| 106.3.5.1.3(1)(3)(4)(6)(10)(13). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |