Plan Review Notes
Plan Review Notes For Permit 09090357
Permit Number 09090357
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-09-28 13:15:30*****DENIED*****
  
 THE APPROROPIATE PLAN SHEETS (A-5, E-1 & E-2) TO BE
 FIRE-STAMPED WHEN THE FOLLOWING HAVE BEEN ADDRESSED:
  
 1. ON SHEET A-5, THE CORRIDORS (104, 112, 119) LEAD TO
 A REAR DOOR. WHERE DO THESE DOORS LEAD TO AND ARE THEY
 CONSIDERED EXIT DOORS?
  
 2. ON SHEET A-5, THERE APPEARS TO BE NO FIRE PROTECTION
 FOR THE CONFERENCE ROOM AND OPEN OFFICE AREAS.
  
 3. THE OTHER PLAN REVIEWERS COMMENTS HAVE BEEN
 ADDRESSED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW