Plan Review Notes For Permit 09090339 |
Permit Number |
09090339 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-22 14:07:39 | PASSED/PROVISO: | | | | REVISIONS REQUIRED PRIOR TO ROUGH INSPECTION. | | | | 1. SHT 3.1 TOILET ROOM #130 SHALL BE ACCESSIBLE. | | SECTION 11-4.3(11). SUBMIT A DETAIL SHOWING COMPLIANCE | | WITH SECTIONS 11-4.16, 11-4.17, 11-4.19 & 11-4.22 WITH | | ALL SUBSECTIONS AS WELL AS FIGURES 28 & 31. (SHOW | | TURNING AREA IN TOILET ROOM). | | | | 2. SHT 3.1 DETAILS 12 & 19 CLEARANCES PER SECTION | | 11-4.19.2 ARE TO BE 2'5" AT THE APRON. DETAILS SHOW THE | | BOTTOM OF THE APRON AT 2'3". | | | | 3. SHT 3.1 DETAIL 14 SUBMIT A DETAIL FOR THE DRINKING | | FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH | | ALL SUBSECTIONS. | | | | 4. SHTS 3.1 & 8.1 DETAIL 20 SHOW CLEAR FLOOR SPACE FOR | | THE BREAK ROOM SINK. FORWARD APPROACH REQUIRED. SECTION | | 11-4.24.5. | | | | 5. SHT 8.1 DETAIL 16. THE CABINET DOORS ARE NOT | | APPROVED IN THE CLEAR FLOOR SPACE FOR THE FIXTURE. | | PLEASE DELETE FROM ELEVATION. SECTION 11-4.24.5. THE | | DETAIL SHALL ALSO SHOW THE KNEE CLEARANCE, 11-4.24.3 & | | DETAIL FOR EXPOSED PIPES & SURFACES PER SECTION | | 11-4.24.6. | | | | 6. SHT M-2 WATER HAMMER ARRESTORS SHALL BE INSTALLED | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE | | CEILING AS SHOWN. PDI-WH 201. | | | | |
|