Plan Review Notes
Plan Review Notes For Permit 09090339
Permit Number 09090339
Review Stop P
Sequence Number 1
Notes
Date Text
2009-09-22 14:07:39PASSED/PROVISO:
  
 REVISIONS REQUIRED PRIOR TO ROUGH INSPECTION.
  
 1. SHT 3.1 TOILET ROOM #130 SHALL BE ACCESSIBLE.
 SECTION 11-4.3(11). SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.17, 11-4.19 & 11-4.22 WITH
 ALL SUBSECTIONS AS WELL AS FIGURES 28 & 31. (SHOW
 TURNING AREA IN TOILET ROOM).
  
 2. SHT 3.1 DETAILS 12 & 19 CLEARANCES PER SECTION
 11-4.19.2 ARE TO BE 2'5" AT THE APRON. DETAILS SHOW THE
 BOTTOM OF THE APRON AT 2'3".
  
 3. SHT 3.1 DETAIL 14 SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH
 ALL SUBSECTIONS.
  
 4. SHTS 3.1 & 8.1 DETAIL 20 SHOW CLEAR FLOOR SPACE FOR
 THE BREAK ROOM SINK. FORWARD APPROACH REQUIRED. SECTION
 11-4.24.5.
  
 5. SHT 8.1 DETAIL 16. THE CABINET DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE FOR THE FIXTURE.
 PLEASE DELETE FROM ELEVATION. SECTION 11-4.24.5. THE
 DETAIL SHALL ALSO SHOW THE KNEE CLEARANCE, 11-4.24.3 &
 DETAIL FOR EXPOSED PIPES & SURFACES PER SECTION
 11-4.24.6.
  
 6. SHT M-2 WATER HAMMER ARRESTORS SHALL BE INSTALLED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201.
  
  