2009-09-26 12:57:26** DENIED **
  
 1) NOTE: PLANS NEED TO CONTAIN THE FOLLOWING ADOPTED
 RELEVANT CODES FOR DESIGN. PLANS CONTAIN DESIGN
 REFERENCE TO THE 2004 FBC WITH 2007 REVISIONS. ALTHOUGH
 PLANS NEED TO BE UNDER THE DESIGN OF THE 2007 FBC.
 PLANS ALSO NOTE 2003 NFPA-101. HOWEVER AS PER THE NEW
 ADOPTED 2007 FBC AS WELL AS FAC69A-3.012, 69A-60.003,
 .004 THE CURRENT ADOPTED NFPA-101 SINCE DECEMBER
 31ST,2008 IS THE 2006 EDITION.
 2005 NFPA-70 ( NEC)
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
  
 ** PLEASE ADJUST
  
  
 2) NOTE: PLEASE SEE 13-415.AB.5. A METHOD *A* WAS
 SUBMITTED ALONG WITH PLANS SHOWING METHOD *B* FOR
 PRESCRIPTIVE. SECTION AS NOTED DOES NO ALLOW USE OF
 BOTH METHODS.
 THE WATTAGES ON THE INPUT DATA REPORT OF THE SUBMITTED
 METHOD A DO NOT COORDINATE WITH THE PLANS. SEE
 RESTROOMS FOR EXAMPLE WHICH INDICATE A HIGHER DESIGN
 WATTAGE ON PLANS THAN ON THE IDR.
 PLANS ALSO CONTAIN REFERENCES TO FBC WHICH WERE FROM
 THE 2004 FBC.
  
 3) NOTE: PLEASE BE SURE THE ASTRONOMICAL TIME CLOCK AS
 SHOWN CONTAIN THE MINIMUM REQUIRED BATTERY/PROGRAMMING
 BACK UP PER FBC13-415.AB.1.4
  
 4) NOTE: ELECTRIC WATER HEATER NEEDS TO CONTAIN
 SEPARATION FROM COMBUSTIBLES PER 422.17
  
 5) NOTE: STORAGE TYPE OF WATER HEATERS ARE CONTINUOUS
 LOADS WHICH REQUIRES THE LOAD TO BE FIGURED AT 125%.
 422.13
  
 IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved