Plan Review Notes
Plan Review Notes For Permit 09090324
Permit Number 09090324
Review Stop E
Sequence Number 1
Notes
Date Text
2009-11-18 12:57:16PROVISO
 REVISION REQUIRED TO CORRECT THE FOLLOWING.
  
 1) REMOVE EQUIPMENT GROUND FROM METER TO DISCONNECT.
 250.24(A) (5).
  
 2} GROUNDING ELECTRODE MUST BE A #4. 250.66
  
 3} HVAC CALCULATION INCORRECT IN THE LOAD CALCULATION.
 220.82 AND OR 220.83.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  