Plan Review Notes
Plan Review Notes For Permit 09090315
Permit Number 09090315
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-04-29 12:42:45*****APPROVED W/REMINDERS*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS 5.0, 5.2, 5.3, 5.4, 6.1, AND 7.0
 WERE STAMPED, INITIALED, AND DATED. THE FOLLOWING
 REMINDERS WERE ATTACHED AS FOLLOWS:
  
  
  
 SHEET 7.0
 * ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH/STROKE (AS PER WEST PALM
 BEACH CODE)
  
  
 SHEET 5.3
 * INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A IN STAIRWAYS, CORRIDORS, AND LOBBIES; IN ALL
 OTHER OCCUPIED ARES, INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B
 * INTERIOR FLOOR FINISH SHALL COMPLY WITH 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE, IN ACCORDANCE WITH NFPA 101,
 LIFE SAFETY CODE, 2006 EDITION.
  