Plan Review Notes
Plan Review Notes For Permit 09090315
Permit Number 09090315
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-07 07:21:19 
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SUITABLE EXITS ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 3. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6 "
 HIGH AND AT LEAST 1" WIDE SHALL BE PROVIDED. THESE
 NUMBERS SHOULD CONTRAST WITH THE BACKGROUND THEY ARE
 AFFIXED TO.
  
 4. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 5. PLANS INDICATE A CHANGE OF USE FROM A B TO A D
 OCCUPANCY.
  
 6. PLANS DO NOT ILLUSTRATE ANY SAFETY SYSTEMS OR
 DEVICES. THESE INCLUDE ILLUMINATED EXIT SIGNS,
 EMERGENCY LIGHTS, SMOKE ALARMS, AND PORTABLE FIRE
 EXTINGUISHERS.
  
 7. BATHROOM DOORS SHALL BE OPERABLE FROM OUTSIDE THESE
 ROOMS.
  
 8. CLOSET DOOR LOCKS SHALL BE OPERABLE FROM INSIDE.
  
 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 10. A FIRE ALARM SYSTEM IS REQUIRED. SEPARATE PLANS AND
 PERMITS REQUIRED PRIOR TO INSTALLATION.
  
 11. PLEASE INDICATE INTERIOR FLOOR FINISH.
  
 12. PLEASE INDICATE THE TYPES OF DOOR HARDWARE AND ANY
 LOCKING DEVICES.
  
 13. PLEASE INDICATE TREAD DEPTH FOR STAIR TREADS.
  
 14. AN EMERGENCY PLAN SHALL BE STARTED AS IT WILL NEED
 TO BE COMPLETED PRIOR TO OPENING.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION