Plan Review Notes For Permit 09090315 |
Permit Number |
09090315 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-07 07:21:19 | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 2. SUITABLE EXITS ARE TO BE PROVIDED DURING | | CONSTRUCTION. | | | | 3. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6 " | | HIGH AND AT LEAST 1" WIDE SHALL BE PROVIDED. THESE | | NUMBERS SHOULD CONTRAST WITH THE BACKGROUND THEY ARE | | AFFIXED TO. | | | | 4. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR ALL HANDRAILS AND GUARDRAILS. | | | | 5. PLANS INDICATE A CHANGE OF USE FROM A B TO A D | | OCCUPANCY. | | | | 6. PLANS DO NOT ILLUSTRATE ANY SAFETY SYSTEMS OR | | DEVICES. THESE INCLUDE ILLUMINATED EXIT SIGNS, | | EMERGENCY LIGHTS, SMOKE ALARMS, AND PORTABLE FIRE | | EXTINGUISHERS. | | | | 7. BATHROOM DOORS SHALL BE OPERABLE FROM OUTSIDE THESE | | ROOMS. | | | | 8. CLOSET DOOR LOCKS SHALL BE OPERABLE FROM INSIDE. | | | | 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | WALLS AND CEILINGS. | | | | 10. A FIRE ALARM SYSTEM IS REQUIRED. SEPARATE PLANS AND | | PERMITS REQUIRED PRIOR TO INSTALLATION. | | | | 11. PLEASE INDICATE INTERIOR FLOOR FINISH. | | | | 12. PLEASE INDICATE THE TYPES OF DOOR HARDWARE AND ANY | | LOCKING DEVICES. | | | | 13. PLEASE INDICATE TREAD DEPTH FOR STAIR TREADS. | | | | 14. AN EMERGENCY PLAN SHALL BE STARTED AS IT WILL NEED | | TO BE COMPLETED PRIOR TO OPENING. | | | | DENIED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|