2009-10-31 12:25:36BUILDING REVIEW COMMENTS
  
  
 1)
 PROVIDE DRAWINGS FOR SCOPE OF WORK ONLY OR CHANGE
 PERMIT APPLICATION DESCRIPTION TO INCLUDE ALL WORK
 SHOWN ON DRAWINGS.
  
 2)
 THE 2007 FLORIDA ACCESSIBILITY CODE REQUIRES THE
 FOLLOWING,
 11-4.5.2 ACCESSIBLE ENTRANCE AT THE DOORWAY SHALL NOT
 EXCEED 1/2" ELEVATION CHANGE.
 11-4.8.3 RAMPS THAT ARE PART OF A MEANS OF EGRESS TO BE
 MIN. 44" WIDE.
 11-4.8.4 PROVIDE 60" CLEAR LANDING AT THE TOP AND 72"
 STRAIGHT RUN AT THE BOTTOM OF THE RAMP.
  
 3)
 A CHANGE OF USE APPLICATION WILL BE REQUIRED FOR A DAY
 CARE OCCUPANCY.
  
 4)
 A RIGHT OF WAY PERMIT WILL BE REQUIRED FOR ANY
 ALTERATIONS TO THE CITY CURB AND SIDEWALK.
  
  