2009-09-23 09:08:06 | |
| ** DENIED ** |
| |
| ** ** THERE IS CONFUSION OVER SCOPE OF WORK. THE PLANS |
| SHOW SEVERAL NEW ITEMS HOWEVER A NOTE ON PLANS STATES |
| ITEMS ARE EXISTING UNLESS OTHERWISE NOTED. THE PLANS |
| DON???T INDICATE WHAT ALREADY EXISTS AND WHAT IS NEW. |
| IF ELECTRICAL ALREADY EXISTS IN ANY PARTICULAR LOCATION |
| IT IS TYPICALLY LABELED WITH AN *E* FOR EXISTING. WHEN |
| ELECTRICAL ON PLANS ARE NOT NOTED WITH AN E OR N TO |
| DIFFERENTIATE BETWEEN THE TWO THEN EVERYTHING IS LOOKED |
| AT AS BEING NEW TO BE INSTALLED. IN EITHER CASE THERE |
| ARE COMMENTS BELOW WHICH MAY BE HANDLED BY INDICATING |
| EXISTING OR THEY MAY NEED TO BE INSTALLED AS NEW. |
| |
| 1) NOTE: PLANS CONTAIN A NOTE TO ELECTRICAL WIRING PER |
| CODE. HOWEVER NO SPECIFIC CODE WAS STATED ON PLANS FOR |
| APPLICATION DATE. PER FS 553.73, FBC 2007 WITH 2009 |
| REVISIONS THE FOLLOWING CODES IS THE CURRENT ADOPTED |
| CODES WHICH SHOULD BE STATED ON PLANS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE 210.63 FOR MISSING RECEPTACLE FOR |
| CONDENSING UNITS. ALSO 210.8A3 FOR GFI PROTECTION. |
| |
| 3) NOTE: PLEASE SEE FBC R313.1,313.2, 313.2.1 FOR SMOKE |
| ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO CURRENT |
| CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR REQUIRED |
| LOCATIONS. |
| PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN |
| 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC |
| REQUIREMENTS. ( OUTSIDE MASTER BEDROOM) |
| |
| 4) NOTE: PANEL SCHEDULE ONLY INDICATE ONE A/C SYSTEM |
| YET THE PLANS INDICATES TWO. |
| TWO CU ARE SHOWN HOWEVER NO LOCATIONS FOR AH UNITS. |
| PLEASE BE SURE TO SEE 440.11, 440.12 FOR REQUIRED |
| DISCONNECTS. PLEASE ALSO SEE 210.70 IF THESE UNITS ARE |
| LOCATED IN ATTIC AREAS. |
| ** PLEASE SEE NOTE BELOW WITH RESPECT TO COMPLETE PANEL |
| SCHEDULE AS THERE IS A SYSTEM MISSING FROM PANEL. |
| |
| 5) NOTE: PLEASE SEE 210.52E, 210.8A3 FOR MISSING FRONT |
| AND REAR RECEPTACLES. IF ONE MEETING THE REQUIREMENT |
| FOR CU IS PLACED AT REAR THIS MAY SERVE AS THE SAME. |
| IF EXISTING |
| |
| 6) NOTE: RISER INDICATES AN * EQUIPMENT GROUNDING |
| CONDUCTOR* BEING INSTALLED FROM METER TO THE FIRST |
| MEANS OF DISCONNECT. THIS IS NOT PERMITTED PER 250.6, |
| 250.24. AS THE FIRST MEANS OF DISCONNECT IS BONDED YOU |
| WOULD NOT BRING AN EQUIPMENT GROUNDING CONDUCTOR AS |
| THIS WOULD PARALLEL THE NEUTRAL. THIS CREATES |
| OBJECTIONABLE CURRENTS |
| |
| 7) NOTE: A NEW DOOR IS BEING INSTALLED FROM AN EXISTING |
| WINDOW WHICH IS CREATING A NEW EXIT TO OUTSIDE. THIS |
| REQUIRES A NEW LIGHT AND LIGHTING OUTLET CONTROL. |
| 210.70 |
| |
| 8) NOTE: PLEASE SEE KITCHEN PLANS AS PROVIDED. THERE IS |
| A SWITCH ON THE WALL WHICH DOES NOT CONNECT TO |
| ANYTHING. WHAT DOES THIS DO? |
| 210.70? |
| |
| 9) NOTE: PLEASE PROVIDE A COMPLETE PANEL SCHEDULE AND |
| LOAD CALCULATIONS PER NEC. PLEASE SEE NEC 220 FOR |
| RESIDENTIAL. SOME SPECIFIC SECTIONS WOULD BE 220.10, |
| 220.12, 220.42, 220.52, ETC |
| SEE NEXT COMMENT ALSO. |
| |
| 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER |
| HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC |
| COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR |
| SERVICE AND FEEDERS THIS IS CONSIDERED A CONTINUOUS |
| LOAD. THIS MEANS THE WATER HEATER 4500VA SHALL BE |
| FIGURED AT 125% INTO LOAD CALCULATIONS. |
| |
| 11) NOTE: PLEASE PROVIDE AIC RATING FOR NEW SERVICE |
| EQUIPMENT. 110.9 |
| |
| 12) NOTE: THE RISER INDICATES A #4 /0 FOR GROUNDING |
| ELECTRODE. THE SYMBOL USED LENDS THIS TO BEING A |
| CONDUCTOR MUCH LARGE THAN NEEDED. THIS MAY BE A |
| MISPRINT OF SOME KIND? |
| |
| 13) NOTE: RISER ALSO INDICATES ATTACHMENT TO BUILDING |
| STEEL. IF THIS CONNECTION IS NOT ALREADY DONE, IT IS |
| NOT REQUIRED BY 250.50 TO CHIP OUT THE EXISTING FOOTER |
| STEEL TO ATTACH. THE AMOUNT OF STEEL AND CONNECTION |
| POINT OF EXISTING STEEL WOULD NOT BE KNOWN. THIS WOULD |
| ALSO AFFECT THE STRUCTURAL INTEGRITY OF THE EXISTING |
| FOOTER. |
| IF SHOWN ON PLANS, THEN IT WOULD BE EXPECTED TO ATTACH. |
| PLEASE CALL TO GO OVER IF NEEDED. |
| |
| 14) NOTE: PLEASE PROVIDE A MORE ACCURATE PANEL |
| SCHEDULE. THERE IS ONLY ONE LIGHTING CIRCUIT SHOWN ON |
| PANEL SCHEDULE. YET SOME OTHERS SUCH AS 2-POLE BREAKERS |
| SHOWN FOR SMALL APPLIANCES AND 2-POLE BREAKER FOR |
| BATHROOM ARE NOT CLEAR. |
| PLEASE SEE 408.4 AND UPDATE. |
| |
| |
| ** AS ELECTRICAL ON SHEET IS MISSING SOME INFORMATION, |
| THERE MAY BE SOME ITEMS NOT YET SUBMITTED WHICH MAY |
| CREATE CODE COMMENTS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |