Plan Review Notes
Plan Review Notes For Permit 09090246
Permit Number 09090246
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-23 09:08:06 
 ** DENIED **
  
 ** ** THERE IS CONFUSION OVER SCOPE OF WORK. THE PLANS
 SHOW SEVERAL NEW ITEMS HOWEVER A NOTE ON PLANS STATES
 ITEMS ARE EXISTING UNLESS OTHERWISE NOTED. THE PLANS
 DON???T INDICATE WHAT ALREADY EXISTS AND WHAT IS NEW.
 IF ELECTRICAL ALREADY EXISTS IN ANY PARTICULAR LOCATION
 IT IS TYPICALLY LABELED WITH AN *E* FOR EXISTING. WHEN
 ELECTRICAL ON PLANS ARE NOT NOTED WITH AN E OR N TO
 DIFFERENTIATE BETWEEN THE TWO THEN EVERYTHING IS LOOKED
 AT AS BEING NEW TO BE INSTALLED. IN EITHER CASE THERE
 ARE COMMENTS BELOW WHICH MAY BE HANDLED BY INDICATING
 EXISTING OR THEY MAY NEED TO BE INSTALLED AS NEW.
  
 1) NOTE: PLANS CONTAIN A NOTE TO ELECTRICAL WIRING PER
 CODE. HOWEVER NO SPECIFIC CODE WAS STATED ON PLANS FOR
 APPLICATION DATE. PER FS 553.73, FBC 2007 WITH 2009
 REVISIONS THE FOLLOWING CODES IS THE CURRENT ADOPTED
 CODES WHICH SHOULD BE STATED ON PLANS.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 210.63 FOR MISSING RECEPTACLE FOR
 CONDENSING UNITS. ALSO 210.8A3 FOR GFI PROTECTION.
  
 3) NOTE: PLEASE SEE FBC R313.1,313.2, 313.2.1 FOR SMOKE
 ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO CURRENT
 CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR REQUIRED
 LOCATIONS.
 PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN
 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC
 REQUIREMENTS. ( OUTSIDE MASTER BEDROOM)
  
 4) NOTE: PANEL SCHEDULE ONLY INDICATE ONE A/C SYSTEM
 YET THE PLANS INDICATES TWO.
 TWO CU ARE SHOWN HOWEVER NO LOCATIONS FOR AH UNITS.
 PLEASE BE SURE TO SEE 440.11, 440.12 FOR REQUIRED
 DISCONNECTS. PLEASE ALSO SEE 210.70 IF THESE UNITS ARE
 LOCATED IN ATTIC AREAS.
 ** PLEASE SEE NOTE BELOW WITH RESPECT TO COMPLETE PANEL
 SCHEDULE AS THERE IS A SYSTEM MISSING FROM PANEL.
  
 5) NOTE: PLEASE SEE 210.52E, 210.8A3 FOR MISSING FRONT
 AND REAR RECEPTACLES. IF ONE MEETING THE REQUIREMENT
 FOR CU IS PLACED AT REAR THIS MAY SERVE AS THE SAME.
 IF EXISTING
  
 6) NOTE: RISER INDICATES AN * EQUIPMENT GROUNDING
 CONDUCTOR* BEING INSTALLED FROM METER TO THE FIRST
 MEANS OF DISCONNECT. THIS IS NOT PERMITTED PER 250.6,
 250.24. AS THE FIRST MEANS OF DISCONNECT IS BONDED YOU
 WOULD NOT BRING AN EQUIPMENT GROUNDING CONDUCTOR AS
 THIS WOULD PARALLEL THE NEUTRAL. THIS CREATES
 OBJECTIONABLE CURRENTS
  
 7) NOTE: A NEW DOOR IS BEING INSTALLED FROM AN EXISTING
 WINDOW WHICH IS CREATING A NEW EXIT TO OUTSIDE. THIS
 REQUIRES A NEW LIGHT AND LIGHTING OUTLET CONTROL.
 210.70
  
 8) NOTE: PLEASE SEE KITCHEN PLANS AS PROVIDED. THERE IS
 A SWITCH ON THE WALL WHICH DOES NOT CONNECT TO
 ANYTHING. WHAT DOES THIS DO?
 210.70?
  
 9) NOTE: PLEASE PROVIDE A COMPLETE PANEL SCHEDULE AND
 LOAD CALCULATIONS PER NEC. PLEASE SEE NEC 220 FOR
 RESIDENTIAL. SOME SPECIFIC SECTIONS WOULD BE 220.10,
 220.12, 220.42, 220.52, ETC
 SEE NEXT COMMENT ALSO.
  
 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC
 COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR
 SERVICE AND FEEDERS THIS IS CONSIDERED A CONTINUOUS
 LOAD. THIS MEANS THE WATER HEATER 4500VA SHALL BE
 FIGURED AT 125% INTO LOAD CALCULATIONS.
  
 11) NOTE: PLEASE PROVIDE AIC RATING FOR NEW SERVICE
 EQUIPMENT. 110.9
  
 12) NOTE: THE RISER INDICATES A #4 /0 FOR GROUNDING
 ELECTRODE. THE SYMBOL USED LENDS THIS TO BEING A
 CONDUCTOR MUCH LARGE THAN NEEDED. THIS MAY BE A
 MISPRINT OF SOME KIND?
  
 13) NOTE: RISER ALSO INDICATES ATTACHMENT TO BUILDING
 STEEL. IF THIS CONNECTION IS NOT ALREADY DONE, IT IS
 NOT REQUIRED BY 250.50 TO CHIP OUT THE EXISTING FOOTER
 STEEL TO ATTACH. THE AMOUNT OF STEEL AND CONNECTION
 POINT OF EXISTING STEEL WOULD NOT BE KNOWN. THIS WOULD
 ALSO AFFECT THE STRUCTURAL INTEGRITY OF THE EXISTING
 FOOTER.
 IF SHOWN ON PLANS, THEN IT WOULD BE EXPECTED TO ATTACH.
 PLEASE CALL TO GO OVER IF NEEDED.
  
 14) NOTE: PLEASE PROVIDE A MORE ACCURATE PANEL
 SCHEDULE. THERE IS ONLY ONE LIGHTING CIRCUIT SHOWN ON
 PANEL SCHEDULE. YET SOME OTHERS SUCH AS 2-POLE BREAKERS
 SHOWN FOR SMALL APPLIANCES AND 2-POLE BREAKER FOR
 BATHROOM ARE NOT CLEAR.
 PLEASE SEE 408.4 AND UPDATE.
  
  
 ** AS ELECTRICAL ON SHEET IS MISSING SOME INFORMATION,
 THERE MAY BE SOME ITEMS NOT YET SUBMITTED WHICH MAY
 CREATE CODE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  