Plan Review Notes For Permit 09090224 |
Permit Number |
09090224 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-15 10:45:08 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- FLAT ROOF SYSTEM: | | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION FROM NOA 07-0822.10 SUBMITTED IS | | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA | | RESIDENTIAL CODE. | | | | B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON NOA 07-0822.10 SUBMITTED. | | | | C) RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | | | D) DESIGN PROFESSIONAL DOING RAS 117 CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. | | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA | | RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE | | "C", NOT "B". | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | SEC. 713.13 FLORIDA STATUTE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|