2010-05-03 16:35:04BUILDING PLAN REVIEW
 PERMIT: 09090218
 ADD: 5011 BROADWAY AV
 CONT: TO BE DETERMINED
 TEL: (786)368-6455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE W/ 2009
 SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 DATE MAY 03 /2010
 SHEET A-1 SITE PLAN NOTES & CODE INFORMATION:
  
 1) A-E COMPLIED.
 F) IF THIS PERMIT IS TO BE PHASED PLEASE PROVIDE TIME
 LINES FOR EACH PHASE, THE BUILDING OFFICIAL MAY REQUIRE
 SEPARATE PERMITS DEPENDING ON THE PHASED TIME LINE.
  
 2) NOTE PRODUCT APPROVALS ARE NOT REQUIRED AT TIME OF
 PERMIT ISSUANCE BUT WILL BE CONSIDERED A REVISION AND A
 SEPARATE REVIEW AND ASSOCIATED FEES
 WOULD BE REQUIRED.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE
 AS FOLLOWS:
 A) FIXED GLASS/ STORE FRONT
 B) EXTERIOR GLAZED SWING DOORS & SIDELIGHTS
 C) SINGLE EXTERIOR HOLLOW METAL SWING DOORS
 D) PAIRS OF EXTERIOR HOLLOW METAL SWING DOORS
 E AUTOMATIC SLIDING DOORS& SIDE LIGHTS
 F) TRUSS ANCHORS
 G) WALL LOUVERS- DECORATIVE SHUTTERS
 H) EFIS WALL SYSTEMS
 I) SHUTTERS BAHAMAN STYLE- ON TOWERS
 J) ROOF ASSEMBLY???S UNDERLAYMENT, MODIFIED BITUMEN &
 ROOF TILE
  
 3A) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
  
 4) 2ND REQUEST, FLOOR PLAN A-3 INDICATES USE OF POWER
 HORIZONTAL SLIDING DOORS. SHOW COMPLIANCE WITH:
 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN
 GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED
 TO BE A COMPONENT OF A MEANS OF EGRESS IN
 ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 SHALL
 COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
 2. THE DOORS SHALL BE OPEN ABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4. THE DOOR SHALL BE OPERABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY
 SMOKE DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 80 AND SHALL COMPLY WITH SECTION 715 .
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 RESPONSE FROM THE DESIGN PROFESSIONAL WAS TO SITE THE
 CODE SECTION NOT TO PRODUCE MANUFACTURER???S SPEC OF
 DOOR INDICATING COMPLIANCE. 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 5A) 2ND REQUEST, THE FOLLOWING ITEMS WILL DEAL WITH
 ROOFING REPORTS BE ADVISED OF THE INFORMATION THAT WILL
 NEED TO BE HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 5B) 2ND REQUEST, ROOF TILE FOR SLOPED ROOFS, PLEASE
 INDICATE WHICH FASTENING SYSTEM SHALL BE USED.106.1.2
 ADDITIONAL INFORMATION REQUIRED. MOMENT OF OVERTURNING,
 1609.7.3 RIGID TILE.
  
 5C) 2ND REQUEST, NO INFORMATION FOR FASTENING OF HIP
 BOARD OR HIP TILE. 1507.3.8 APPLICATION. TILE SHALL BE
 APPLIED ACCORDING TO THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08-05 (FOURTH EDITION).
  
 6A) COMPLIED.
  
 6B)2ND REQUEST, STRAPPING OVER THE UNIT DOES NOT
 CONSTITUTE MEETING THIS CODE SECTION. 301.13 FBC
 MECHANICAL. WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST WIND PRESSURES ON
 THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 THIS CODE SECTION IS NOT ONLY FOR THE ATTACHMENT OF THE
 UNIT TO THE STRUCTURAL MEMBERS BUT THE ACTUAL
 MECHANICAL EQUIPMENT ITSELF, THE EXTERIOR CABINETRY.
  
 7A-B) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10)2ND REQUEST, AT CONTRACTORS OWN RISK!!! SHEET S-4
 PLEASE INDICATE COMPLIANCE WITH 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 11)COMPLIED
  
 12) 2ND REQUEST, SHEET S-4 CODES AND SPECIFICATIONS ALL
 WORK SHALL BE IN ACCORDANCE WITH 2007 FBC HIGH WIND
 VELOCITY ZONE, PLEASE NOT THE HIGH VELOCITY WIND ZONE
 DESIGNATION IS ONLY TO BE USED FOR DADE AND BROWARD
 COUNTIES, THE CITY OF WEST PALM BEACH IS LOCATED IN THE
 HIGH WIND DEBRIS REGION PLEASE REVIEW FIGURE 1609. THE
 WIND DESIGN FOUND ON SHEET S-2 INDICATES 146MPH,
 EXPOSURE "C" WHICH IS A DADE AND BROWARD REQUIREMENT
 FOR THE HIGH WIND VELOCITY ZONE. IF THE DESIGNER
 WHISHES TO DESIGN TO THIS MORE STRINGENT REQUIREMENT,
 THEN THE ASSOCIATED HIGHER POSITIVE & NEGATIVE
 PRESSURES MUST BE USED IN THE WIND DESIGN.
  
 12A-C) COMPLIED.
  
 13) SEE NOTE# 4 SAME QUESTION.
  
 14) 2ND REQUEST, PROVIDE INFORMATION ON THE WALK-IN
 COOLERS AND FREEZERS. 2603.4.1.2 COOLER AND FREEZER
 WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF
 10 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL:
 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE SPRINKLED.
  
 2603.4.1.3 WALK-IN COOLERS. IN NON-SPRINKLED BUILDINGS,
 FOAM PLASTIC HAVING A THICKNESS THAT DOES NOT EXCEED 4
 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK-IN
 COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR AREA
 DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) SHEET A-7 INDICATES VARIOUS SECTIONS THROUGH THE
 STRUCTURE WITH FINISHES( 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS ;
 15A) PLANS ARE NOT COMPLETE AS TO INTERIOR FINISHES OF
 ROOMS
  
 15B) COMPLIED.
  
 15C) A V-B BUILDING TYPE WILL NOT REQUIRE FIRE RATED
 CEILINGS. THE QUESTION WAS WILL THEY BE NEEDED, NO THEY
 WOULD NOT BE REQUIRED BECAUSE OF THE AREA INCREASES
 PROVIDED BY THE NFPA 13 SPRINKLER SYSTEM..
  
 15D) COMPLIED.
  
 16) PROVISO: TRUSS PLANS WERE NOT SUBMITTED, PLANS FAIL
 TO PROVIDE LOADS TO BE RESISTED, HORIZONTAL, LATERAL
 AND GRAVITY LOADS.
  
 17) NEW COMMENT: THIS BUILDING WILL REQUIRE 2 EXITS AT
 LEAST 1/3RD THE DISTANCE APART. 1015.2.1. THE REAR
 DOORS AS IS CAN NOT BE USED AS AN EXIT SINCE THEY LEAD
 INTO A STORAGE OCCUPANCY.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved