Plan Review Notes For Permit 09090218 |
Permit Number |
09090218 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-22 14:41:43 | FAILED | | | | 1) THE LANDSCAPE PLANS DO NOT SHOW THE SAME CONDITIONS | | AS THE SITE PLAN, SPECIFICALLY, THE DIMENSIONS OF THE | | LANDSCAPE AREA AND CURB LOCATIONS ON THE NORTH SIDE OF | | THE BUILDING, AND THE INTERIOR PARKING AREA ON THE | | SOUTH SIDE OF THE BUILDING. | | | | 2) THE PHOTOMETRIC PLAN SHALL SHOW THE FOOT CANDLE | | LEVELS AT THE WEST PROPERTY LINE - THIS SHALL NOT | | EXCEED 0.5 FOOT CANDLES. | | | | 3) THE BMUD TYPE II REGULATIONS REQUIRE THAT THE | | FINISHED FLOOR TO FINISHED CEILING OF THE GROUND FLOOR | | BE AT LEAST 12 FEET - SHEET A-7 SHOWS THE CEILING | | HEIGHT OF 11 FEET 2 INCHES. | | | | 4) THE LIGHT POST LOCATIONS SHALL BE SHOWN ON THE | | LANDSCAPE PLAN. PLEASE NOT THAT THERE APPEARS TO BE A | | TREE - POST CONFLICT ALONG THE WEST PROPERTY LINE. | | | | 5) ANY NEW FENCES OR WALLS, EXCLUDING THE CART RETURN | | SCREEN, SIGNAGE, AND THE BENCHES REQUIRE SEPARATE | | PERMITS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|