Plan Review Notes
Plan Review Notes For Permit 09090218
Permit Number 09090218
Review Stop P
Sequence Number 1
Notes
Date Text
2009-09-30 10:22:13DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-4 & P-2 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE THE TOTAL SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN, GUTTER &
 DOWNSPOUT. CALCULATIONS SHALL SHOW 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS AS WELL AS THE AREA
 OF A ROOF DRAINING ON TO THE ROOF FROM ABOVE ADDED TO
 EACH AREA. THE GUTTER AND DOWNSPOUT SIZE SHALL BE
 INDICATED. TABLES 1106.2 & 1106.6.
  
 2. ALL SHEETS WITH RUIZ - BRITO TITLE BLOCK SHALL
 INCLUDE THE FIRM LICENSE NUMBER PER FAC 61G1-16.004(2)
 AND THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 PER FAC 61G1-16.004(7). FS 481.219 & 481.2055.
  
 3. SHTS A-8, P-1 & P-4 INDICATE GAS HEATER &
 APPLIANCES. SEE GAS REVIEW FOR SEPARATE GAS
 PERMIT/PLANS/REQUIRMENTS.
  
 4. SHT P-1 FLOOR DRAINS IN THE MEAT CUTTING/STORAGE
 AREAS. THE MAXIMUM DISTANCE FROM THE 3" FLOOR DRAINS TO
 THE VENT IS 12 FEET PER TABLE 906.1. THE FLOOR DRAINS
 PER THE 1/8TH SCALE ARE INDICATED AS BEING 14 TO 16
 FEET FROM THE VENT.
  
 5. SHT P-1 DELI AREA NOTE STATES "8 INCH RWL 4,962 SF",
 BUT NO ROOF DRAIN IS SHOWN. PLEASE CLARIFY. SECTION
 106.1.1 & TABLE 1106.3.
  
 6. SHTS P-1 & P-3 INDICATE NEW FIXTURES DRAINING INTO
 THE EXISTING GREASE INTERCEPTOR. THE GREASE INTERCEPTOR
 SHALL BE INSPECTED FOR SIZE AND TO MAKE SURE IT IS
 OPERATING PROPERLY. ARTICLE III SECTION 90-124(7).
 PLEASE CONTACT HOLLY MCGRATH LABORATORY SUPERVISOR,
 PUBLIC UTILITIES DEPARTMENT FOR INSPECTION AND APPROVAL
 OF EXISTING GREASE INTERCEPTOR. A WRITTEN DETERMINATION
 IS REQUIRED PRIOR TO PERMIT BEING ISSUED.
  
 7. SHT P-4 WATER ISOMETRIC. AIR CHAMBERS SHOWN AT EACH
 FIXTURE ARE NOT APPROVED. PLEASE DELETE FROM ISOMETRIC.
 PDI-WH 201.
  
 8. SHT P-5 PLUMBING NOTES # 9. AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201.
  
 9. SHT P-5 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 10. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE BUILDING. PLEASE INDICATE IF THERE IS AN
 EXISTING RPZV BACKFLOW OR IF A BACKFLOW WILL BE
 INSTALLED. SECTION 608.13.2.
  
 11. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN. ALSO SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 12. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  