Plan Review Notes
Plan Review Notes For Permit 09090218
Permit Number 09090218
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-14 14:55:13CITY MARKET
 PERMIT NUMBER 09090218
  
 1. THE EXISTING BUILDING EXCEEDS 12,000 SQUARE FEET.
 DURING PHASE 1, PHASE 2, AND PHASE 3 THE ENTIRE STORE
 WILL EXCEED T12,000 SQUARE FEET. THE ENTIRE BUILDING
 WILL BE REQUIRED TO BE FIRE SPRINKLER PROTECTED IN
 ACCORDANCE WITH NFPA 13, THE STANDARD FOR AUTOMATIC
 FIRE SPRINKLERS. ALL COOLERS AND FREEZERS WILL BE
 REQUIRED TO BE FIRE SPRINKLER PROTECTED.
  
 2. SITE PLANS FAILS TO ILLUSTRATE ANY NEW OR EXISTING
 FIRE HYDRANTS.
  
 3. DEMOLITION, CONSTRUCTION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. THE BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT
 LEAST 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE
 REQUIRED. THEY ARE TO CONTAST TO THE BACKGROUND THEY
 WILL BE AFFIXED TO.
  
 5. A KNOX-BOX WILL BE REQUIRED.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE SPRINKLER, FIRE ALARM, AND
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 7. PLEASE PROVIDE A LIFE SAFETY PLAN FOR REVIEW.
  
 8. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 9. ADDITIONAL EXIT SIGNS WILL BE REQUIRED IN SALES
 AREA.
  
 10. NOTE # 1 ON PAGE E-5 IS INCORRECT.
  
 11. IT DOES NOT APPEAR THAT ENOUGH FIRE ALARM SIGNALING
 APPLIANCES ARE PRESENT THROUGHOUT THE STORE.
  
 12. PLEASE INDICATE LOCATIONS OF ALL PORTABLE FIRE
 EXTINGUISHERS.
  
 13. PLEASE PROVIDE SUFFICIENT DETAILS REGADING ALL EXIT
 DOORS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX