Plan Review Notes For Permit 09090218 |
Permit Number |
09090218 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-07 16:14:53 | FAILED | | | | PLEASE PROVIDE NEW PROPOSED WATER USAGE FLOW | | CALCULATIONS / DEMANDS: | | | | 1. THE ADDITION OF SEVERAL FOOD PREPARATION, KITCHEN | | AND UTILITIY AREAS FOR PHASE 1 AND PHASE 2 MAY REQUIRE | | AN UPGRADE TO THE EXISTING WATER SERVICES. | | | | 2. PLEASE PROVIDE LOCATION(S), DETAILS AND CAPACITIY OF | | EXISTING GREASE-WASTE TRAPS TO ENSURE CONFORMITY TO | | CWPB'S CONSTRUCTION STANDARDS. | | | | 3. PLEASE RESPOND TO PLUMBING REVIEW STOP NO. 10, | | CONCERNING THE RPZV BACKFLOW REQUIREMENT PER MR. KEN | | STEVENS. | | | | REVIEWED BY EMERY P. FABIAN, ENGINEERING SERVICES, | | 494-1078 [email protected] |
|