Plan Review Notes
Plan Review Notes For Permit 09090218
Permit Number 09090218
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-07 14:04:15 
 ** DENIED **
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED UNDER PERMIT
 APPLICATION HOWEVER NO LICENSED CONTRACTOR HAS BEEN
 SIGNED ON APPLICATION. ONCE ELECTRICAL REVIEW IS FOUND
 TO PASS FOR REVIEW THE REVIEW STATUS WILL STILL REMAIN
 IN FAILED STATUS UNTIL SUCH TIME LICENSED CONTRACTOR(S)
 HAS BEEN DETERMINED ETC
  
 2) NOTE: PLANS ARE NOT SHOWING THE CORRECT ADOPTED
 CODES BY THE STATE OF FLORIDA. PLEASE KNOW THAT AS OF
 MARCH 1ST, 2009 THE STATE ADOPTED THE FOLLOWING AT A
 MINIMUM.
 2007 FBC W/2009 REVISIONS.
 AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED UNDER FAC
 69A-3.012 AND 69A-60.004, .003 THE 2006 NFPA-101, 2006
 NFPA-1. ELECTRICAL PLANS INDICATE THE 2003 NFPA-101
 PLANS SUBMITTED BEFORE OCTOBER 1ST 2009 ARE UNDER THE
 2005 NATIONAL ELECTRICAL CODE. ( NFPA-70).
 PLEASE BE SURE TO LIST THE FOLLOWING MINIMUM CODES ON
 PLANS.
  
 2007 FBC W/2009 REVISIONS
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72 ( IF APPLICABLE FOR BUILDINGS WITH FIRE
 ALARM SYSTEMS)
  
 ** SOME CODE SECTIONS FOR EXAMPLE ON E-1 NOTE #8 IS
 ACTUALLY FROM THE 1996 NEC. THIS CODE SECTION NEEDS TO
 BE REVISED TO THE APPLICABLE SECTION FROM THE 2005 NEC.
  
 3) NOTE: PLEASE SEE FAC 61G1-60.004 FOR MISSING
 REQUIRED INFORMATION IN THE TITLE BLOCKS FOR ARCHITECT
 AND ARCHITECTURAL FIRM.
 PLEASE SEE FS 481.219 FOR REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 IF THERE ARE ANY QUESTIONS ON LICENSING REQUIRED AND
 INFORMATION REQUIRED TO BE LOCATED ON TITLE BLOCKS,
 PLEASE CONTACT THE BOARD OF ARCHITECT'S LEGAL COUNSEL.
  
 4) NOTE: LANDSCAPE ARCHITECTURAL SHEETS. PLEASE SEE FS
 481.319, 321 FOR REQUIRED LICENSING FOR FIRM,
 CORPORATION, PARTNERSHIP ETC.
 ** PLEASE KNOW ANY LANDSCAPE LIGHTING/SITE LIGHTING
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS PER THE
 BUILDING OFFICIAL. HOWEVER BASE PLANS FOR ENERGY CODE
 COMPLIANCE WILL BE REQUIRED TO SHOW CODE COMPLIANCE.
  
  
 5) NOTE: NO PLANS, DOCUMENTS OR INFORMATION SUBMITTED
 FOR LIGHTING PERFORMANCE CALCULATIONS UNDER FBC CHAPTER
 13 WERE SUBMITTED. PLEASE SEE 13-415.AB.5 FOR INTERIOR
 AND 13-415.AB.2.2 FOR EXTERIOR.
 ** AS NOT CALCULATIONS MEETING ENERGY CODE WERE
 SUBMITTED NO REVIEW OF THESE ITEMS COULD BE DONE.
 ** EVEN WHEN A BUILDING DOES NOT MEET THE DEFINITION OF
 A RENOVATION, THE MINIMUM PRESCRIPTIVE REQUIREMENTS OF
 THE ENERGY CODE STILL MUST BE MET.
  
 6) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2, .1.3 AND .1.4
 FOR MINIMUM LIGHTING CONTROLS. BASED ON THE PLANS ITEMS
 SUCH AS SINGLE POLE SWITCHES AS SHOWN ON SYMBOL LEGEND
 AND PLANS DOES NOT MEET MINIMUM REQUIRED.
 *** IT IS IMPORTANT TO SEE SECTIONS NOTED AND TO CALL
 TO GO OVER ANY QUESTIONS.
  
 7) NOTE: PLANS INDICATE PANEL L IN THE MIDDLE OF THE
 STORAGE ROOM WALL. PLEASE RELOCATE AS STORAGE IS NOT
 PERMITTED IN THIS AREA.
 ALSO KNOW THAT PROTECTION OF ELECTRICAL EQUIPMENT IN
 ANY LOCATION WHERE CONTACT OF ROLLING EQUIPMENT/STORAGE
 UNITS COULD DAMAGE ELECTRICAL EQUIPMENT WILL BE
 REQUIRED.
 ** PLEASE VERIFY LOCATION AS THE ENLARGED ELECTRICAL
 ROOM PLANS INDICATES THE *L* PANEL ON THE MAIN
 ELECTRICAL ROOM YET THE PLANS INDICATE THIS SAME PANEL
 IN STORAGE ROOM ON WALL.??
  
 110.26, 110.27B, 408.17, 240.24 ETC.
  
 8) NOTE: THE AIC RATINGS FOR ALL EQUIPMENT, PANELS AND
 BREAKERS NEED TO BE ON PLANS AT THIS TIME. 110.9
 NOTE MENTIONS TO OBTAIN INFORMATION AND VERIFY HOWEVER
 THIS INFORMATION IS READILY AVAILABLE AT THIS TIME.
 SOME RATINGS ARE SHOWN FOR PANELS WITH SERIES RATINGS.
  
 9) NOTE: PLEASE SEE FBC 13-413.AB.2 FOR REQUIRED NOTES
 TO BE PLACED ON PLANS.
  
 10) NOTE: PLEASE SEE FBC 13-413.AB.1 FOR REQUIRED WORST
 CASE VOLTAGE DROP CALCULATIONS REQUIRED.
  
 11) NOTE: COMPLETE LOAD CALCULATIONS WERE NOT
 SUBMITTED/SHOWN PER NEC. HOW WERE LOADS DERIVED?
 PLEASE SEE 220.12,220.14,220.42,220.44, 220.43 FOR
 RECEPTACLES, LIGHTING, TRACK LIGHTING LOADS ETC.
 ** PLEASE BE SURE TO SEE 215.3,230.42 ETC FOR ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125% INCLUDING LARGEST
 MOTOR LOADS.
  
 12) NOTE: IN THE MIDDLE OF E-4 THERE IS A PANEL
 SCHEDULE FOR A/C EQUIPMENT HOWEVER PANEL IS NOT
 IDENTIFIED. ACTUALLY SATES * PANE*. PLEASE ALSO
 COORDINATE THE LOCATION IN WHICH THIS PANEL IS FED
 FROM. THE *PANE* PANEL SCHEDULE STATES IT IS FED FROM
 PANEL DP, YET BASED ON THE RISER THIS IS A PANEL TAPPED
 FROM THE MAIN GUTTER AND NOT FED FROM DP.
 PLEASE ADJUST AND COORDINATE INFORMATION ON RISER.
 215,220,230,240,408 ETC GIVEN AS GENERAL CHAPTERS FOR
 COORDINATION OF ALL INFORMATION.
  
 13) NOTE: SIGN CIRCUIT STILL REQUIRED AT FRONT ENTRANCE
 PER 600.5
  
 14) NOTE: ANY WINDOW AREAS SHALL HAVE SHOW WINDOW
 RECEPTACLES PER 210.62. PLEASE ALSO BE SURE TO ADJUST
 LOAD CALCULATIONS PER 220.43, 220.14
  
 ** AS THERE IS INFORMATION NOT YET SUBMITTED REQUIRED
 FOR MINIMUM CODE COMPLIANCE REVIEW THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  