Plan Review Notes
Plan Review Notes For Permit 09090216
Permit Number 09090216
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-16 19:14:21 
 ** DENIED PLANS**
  
  
 1) NOTE: THE SUBMITTED FORM B DOES NOT MEET
 13-415.AB.5, 13-415.B.1. THE FORM IS NOT COMPLETED FOR
 ANY SPACE OR TYPE OF FIXTURES. THE SPACES ARE IN FACT
 BLANK. IN EITHER CASE IF CHOOSING TO USE ALL FORM B*S
 FOR COMPLIANCE ONE FORM B IS REQUIRED FOR EACH AND
 EVERY SPACE TYPE IN ORDER TO MEET SPACE BY SPACE.
 MUST ONLY MEET PRESCRIPTIVE FOR LIGHTING PERFORMANCE
 CALCULATIONS. IT IS RECOMMENDED CALLING REVIEWER TO GO
 OVER MINIMUM COMPLIANCE.
 IF ADDING LIGHTS TO EXISTING THEN LIGHTING COMPLIANCE
 IS REQUIRED TO BE SHOWN FOR ALL.
 ** THE FIXTURE LEGEND CLEARLY STATES *ALL* FIXTURES ARE
 EXISTING HOWEVER PER THE LIGHTING PLANS THERE ARE *NEW*
 FIXTURES. HOW ARE ALL FIXTURES EXISTING AND NEW?
  
 2) NOTE: PLEASE SEE 422.30,31 FOR REQUIRED
 DISCONNECTING MEANS FOR IWH.
 PLEASE SEE CIRCUIT 701-3 WHICH IS NOTED ON PANEL
 SCHEDULE CONTAINING A LOCK OFF DEVICE. PLEASE SEE
 SECTIONS AND COMMENTARY. A DEVICE SHALL BE PERMANENT TO
 BREAKER. MUST BE AN INTEGRAL PART OF BREAKER. MAY NOT
 BE A *CLIP ON* OR *SNAP ON* TYPE DEVICE. IF THERE IS
 ANY NEED TO CLARIFICATION SEE UPDATED COMMENTARY UNDER
 THE 2008 NEC.
 THE IWH AS CIRCUITED TO 1702.14 DOE NOT CONTAIN ANY
 NOTE AS ABOVE. WHERE IS THE REQUIRED DISCONNECTING
 MEANS?
  
 3) NOTE: NO SOUND LEVELS INDICATED ON FA SHEETS MEETING
 ADA COMPLIANCE PER 11-4.28.1,.2 AND .3.
 PLEASE PROVIDE.
  
 4) NOTE: PLEASE PROVIDE MORE DETAILED INFORMATION ON
 NEW LIGHTING CONTROLS( TIME CLOCK) NOTED ON PLANS.
 13-415.AB.1.1,.1.2.
 PLEASE ALSO BE AWARE, ALL LIGHTING BEING OVER RIDDEN
 SHALL BE SEEN BY THE OCCUPANT OR MEET EXCEPTIONS. (
 PILOT LIGHTS AND INDICATION OF LIGHTING).
  
 5) NOTE: PLANS STATE THE *LATEST EDITION* OF THE
 NATIONAL ELECTRICAL CODE. HOWEVER PER FS 553.73, RULE
 9B-3.047 THE 2008 HAS NOT YET BEEN ADOPTED BY THE STATE
 OF FLORIDA. NOT UNTIL PERMIT APPLICATIONS AFTER OCT
 1ST, 2009.
 PLEASE ALSO BE AWARE THERE ARE OTHER REVISIONS TO THE
 FBC AT THAT DATE.
 PLEASE BE SURE THE PLANS INDICATE THE MINIMUM CODE AS
 FOLLOWS.
 2005 NFPA-70
 2006 NFPA-101
  
 ** PLANS STATE 2007 FBC ON G-1, HOWEVER THERE ARE 2009
 GLITCHES TO THE 2007 FBC WHICH SUBSTANTIALLY REVISED
 THE CODE.
 PLANS ALSO STATE THE 2006 FLORIDA FIRE PREVENTION CODE.
 THIS SHOULD READ 2007 PER FAC 69A-3.012. REVISED
 NFPA-101 AND NFPA-1 IS PER FAC 69A-60.003, .004.
  
  
  
  
 ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY
 COMMENTS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  