Plan Review Notes For Permit 09090186 |
Permit Number |
09090186 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-22 14:25:44 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. INCORRECT WIND EXPOSURE CLASSIFICATION, PLEASE SEE | | DEFINITION OF EXPOSURE C (AND EXPOSURE B) IN FBC R 301, | | ASCE7-05 AND COMMENTARY. PLEASE REVISE TO EXPOSURE C OR | | EXPLAIN RATIONALE. | | |
|