Plan Review Notes For Permit 09090166
Permit Number 09090166
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-22 15:17:53 
 ** DENIED **
  
  
 1) NOTE: PLEASE SUBMIT MORE DETAILED ELECTRICAL PLANS
 PER 2005 NFPA-70. WHEN MEETING EXCEPTIONS UNDER FS
 471.003 AND 481.229 FOR PLANS REQUIRED TO BE DONE BY AN
 ENGINEER OR ARCHITECT. THE PLANS SHALL BE DONE BY
 LICENSED DESIGNER MEETING EXCEPTIONS PER FS 489.
  
 2) NOTE: PLEASE PROVIDE INFORMATION ON ELECTRICAL AT
 LAUNDRY BUILDING. PLEASE SEE 225.31-225.39 AND
 250.32,250.50 FOR REQUIRED DISCONNECTING MEANS AND
 GROUNDING ELECTRODE SYSTEM AT DETACHED BUILDING.
  
 3) NOTE: PLEASE SHOW NEW OR EXISTING DISCONNECTS FOR
 A/C EQUIPMENT PER 440.12,440.11.
  
 ** AS ELECTRICAL ON SHEET IS NOT DETAILED, THERE MAY BE
 SOME ITEMS NOT YET SUBMITTED WHICH MAY CREATE CODE
 COMMENTS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  