Notes |
Date |
Text |
2009-09-22 15:17:53 | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE SUBMIT MORE DETAILED ELECTRICAL PLANS | | PER 2005 NFPA-70. WHEN MEETING EXCEPTIONS UNDER FS | | 471.003 AND 481.229 FOR PLANS REQUIRED TO BE DONE BY AN | | ENGINEER OR ARCHITECT. THE PLANS SHALL BE DONE BY | | LICENSED DESIGNER MEETING EXCEPTIONS PER FS 489. | | | | 2) NOTE: PLEASE PROVIDE INFORMATION ON ELECTRICAL AT | | LAUNDRY BUILDING. PLEASE SEE 225.31-225.39 AND | | 250.32,250.50 FOR REQUIRED DISCONNECTING MEANS AND | | GROUNDING ELECTRODE SYSTEM AT DETACHED BUILDING. | | | | 3) NOTE: PLEASE SHOW NEW OR EXISTING DISCONNECTS FOR | | A/C EQUIPMENT PER 440.12,440.11. | | | | ** AS ELECTRICAL ON SHEET IS NOT DETAILED, THERE MAY BE | | SOME ITEMS NOT YET SUBMITTED WHICH MAY CREATE CODE | | COMMENTS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|