Date Text
2009-09-11 08:08:45** PROVISO **
  
 ** PLEASE SUBMIT BEFORE FINAL ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE LIST ALL MINIMUM CIRCUITS AND OTHER
 CIRCUITS. PLEASE LIST AMPERAGE AND CONDUCTOR SIZES.
 210.52, 310.16, 408.4
  
 2) NOTE: ALL RECEPTACLES SERVING KITCHEN COUNTER SPACES
 SHALL BE GFI/GFI PROTECTED. 210.8A6
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  