2009-12-09 08:57:24** DENIED **
  
 ** SETS OF PLANS SUBMITTED ARE NOT THE SAME.
 ONE SET HAD ALL COMPLETE ELECTRICAL PAGES WHICH WERE
 NOT REQUESTED ON PREVIOUS REVIEW.
 ONE SET HAS PLUMBING SHEETS WHICH ARE NOT IN THE SECOND
 SET??
  
  
 2ND REQUEST
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE TYPE OF BACK
 UP SYSTEM OF THIS GENERATOR. PLEASE SEE DEFINITIONS IN
 NEC/ NFPA-70 2008, 700,701, AND 702.
 PLEASE ALSO SEE 2005 NFPA-110.
 THE BASE BUILDING PLANS WERE ALSO SUBMITTED HOWEVER NOT
 ALL EMERGENCY LIGHTS ON THE FIXTURE LEGEND INDICATE
 BATTERY BACK UP. ALL REQUIRED EMERGENCY BACK UP POWER
 MUST BE FED FROM 700 OR 701 SYSTEMS. IF BATTERY BACK UP
 POWER IS PROVIDED FOR ALL LIFE SAFETY AND LEGALLY
 REQUIRED THEN THIS SYSTEM WOULD BE OPTION STAND-BY.
 IF THIS IS A 700 OR 701 SYSTEM IT MAY NOT RELY ON
 NATURAL GAS AS THE PRIMARY SOURCE FOR THE PRIME MOVER.
 700.12B3, 701.11B3.
 PLEASE REDESIGN SYSTEM IF INDEED FALLING UNDER NFPA-70,
 700,701 OR NFPA-110
  
 ** THERE WAS NO RESPONSE FROM THE DESIGNER OF RECORD TO
 PREVIOUS ELECTRICAL REVIEW COMMENTS. A CALL WAS PLACED
 TO THE ARCHITECT OF RECORD AS THE PHONE NUMBER LISTED
 ON TITLE BLOCK IS NO LONGER IN USE. NEW NUMBER FOR
 ENGINEER WAS OBTAINED FROM ARCHITECT AND LEFT MESSAGE
 ON 12/8 FOR A RETURN CALL.
  
 PLANS WILL REMAIN IN FAILED STATUS UNTIL INFORMATION IS
 PROVIDED OR PLANS ARE REVISED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  