Plan Review Notes
Plan Review Notes For Permit 09090108
Permit Number 09090108
Review Stop B
Sequence Number 2
Notes
Date Text
2009-12-16 11:18:25****CORRECTIONS****
 ****WILL PASS WITH PROVISO UPON REQUEST***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE
 MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY
 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3
 SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM
 BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT
 APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY
 OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C
 REVISED IN FBC2007 AND ASCE7-05).
  
 INSTALLATION IS TO RESIST WIND LOADS (SLIDING,
 OVERTURNING) FBC1609. PROVIDE INSTALLATION
 SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND
 DESIGN CRITERIA PER FBC1603.1.4.
  
 2ND REVIEW:
  
 THE SECOND PORTION OF THE COMMENT WAS ADDRESSED WITH
 THE ENGINEERING FROM PAUL KING, PE.
  
 THE FIRST PORTION OF THE COMMENT HAS NOT BEEN
 ADDRESSED. THE ENGINEERING PROVIDED CALCULATIONS FOR
 THE ATTACHMENT OF THE GENERATOR TO THE SLAB, BUT THE
 COMMENT IS THAT THE ENCLOSURE IS TO MEET WIND DESIGN
 CRITERIA AND THE GENERATOR DOCUMENTATION DOES NOT SHOW
 COMPLIANCE WITH THAT REQUIREMENT.
  
 UPON REQUEST, THIS REVIEW CAN BE PASSED WITH PROVISO,
 REVISION REQUIRED, AT CONTRACTOR'S RISK, SHOW
 COMPLIANCE WITH 140MPH EXPOSURE C FOR GENERATOR
 ENCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved