Plan Review Notes
Plan Review Notes For Permit 09090108
Permit Number 09090108
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-01 08:40:172007 PALM BEACH LAKES BOULEVARD
  
 1. PLEASE INDICATE WHAT SYSTEMS OR DEVICES THE
 GENERATOR WILL SUPPLY POWER TO.
  
 2. PLANS DO NOT INDICATE ANY DOORS OR WINDOW OPENINGS
 LOCATED NEAR THE GENERATOR. PLEASE INDICATE THAT NO
 WINDOW OR DOOR OPENINGS EXIST WITHIN 10 FEET VERTICALLY
 OR HORIZONTALLY OF THE GENERATOR.
  
 3. THE SURVEY APPEARS TO HAVE BEEN PREPARED IN 2007 AND
 IS OVER TWO YEARS OLD.
  
 4. NO DIMENSIONS PROVIDED WHERE THE GENERATOR IS
 PLANNED TO BE INSTALLED AND THE BUILDING. PLEASE
 PROVIDE DIMENSIONS.
  
 5. ALL DRAWINGS IN THE SUBMITTAL PACKAGE ARE COPIES TO
 INCLUDE SIGNATURES.
  
 6. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE. PLEASE DOCUMENT THIS ON THE
 DRAWINGS.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX