Plan Review Notes For Permit 09090108 |
Permit Number |
09090108 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-01 08:40:17 | 2007 PALM BEACH LAKES BOULEVARD | | | | 1. PLEASE INDICATE WHAT SYSTEMS OR DEVICES THE | | GENERATOR WILL SUPPLY POWER TO. | | | | 2. PLANS DO NOT INDICATE ANY DOORS OR WINDOW OPENINGS | | LOCATED NEAR THE GENERATOR. PLEASE INDICATE THAT NO | | WINDOW OR DOOR OPENINGS EXIST WITHIN 10 FEET VERTICALLY | | OR HORIZONTALLY OF THE GENERATOR. | | | | 3. THE SURVEY APPEARS TO HAVE BEEN PREPARED IN 2007 AND | | IS OVER TWO YEARS OLD. | | | | 4. NO DIMENSIONS PROVIDED WHERE THE GENERATOR IS | | PLANNED TO BE INSTALLED AND THE BUILDING. PLEASE | | PROVIDE DIMENSIONS. | | | | 5. ALL DRAWINGS IN THE SUBMITTAL PACKAGE ARE COPIES TO | | INCLUDE SIGNATURES. | | | | 6. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | NATIONAL ELECTRICAL CODE. PLEASE DOCUMENT THIS ON THE | | DRAWINGS. | | | | DENIED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | BUREAU OF FIRE PREVENTION | | 500 NORTH DIXIE HIGHWAY | | WEST PALM BEACH, FLORIDA 33401 | | (561) 804-4709 PHONE | | (561) 804-4774 FAX |
|