2009-10-13 11:16:57 | ** DENIED ** |
| |
| ** ORIGINAL REVIEW WAS DONE ON 9/24 HOWEVER DID NOT GET |
| INTO THE SYSTEM. NOTES ADDED 10/13 |
| |
| |
| 1) NOTE: PLANS SUBMITTED ARE IN FACT PHOTO-COPIES OF |
| SIGNED, DATED AND SEALED ENGINEERED PLANS. MUST CONTAIN |
| ORIGINAL SIGNATURE, DATE AND SEAL PER FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002, FS 471.025 |
| |
| 2) NOTE: RISER INDICATES AN INTERLOCK ENCLOSURE OF SOME |
| TYPE. PLEASE PROVIDE EQUIPMENT SPECS MEETING MINIMUM |
| LISTING PER UL 1081. IT ALSO INDICATES A NOTE #2, FOR |
| WHAT STATES TO BE AS A NEW AUTOMATIC TRANSFER SWITCH. |
| PLEASE REVISE RISER IF THIS IS INDEED GOING TO BE |
| CHANGED OUT. |
| |
| 3) NOTE: NO PANEL SCHEDULE FOR PANEL *E* COULD BE |
| LOCATED. PLEASE SUBMIT SO THAT LOADS CAN BE VERIFIED. |
| IT IS NOT POSSIBLE TO REVIEW FOR MINIMUM SIZING PER |
| 702.5, 220 OF THE NEC AT THIS TIME. |
| |
| 4) NOTE: PLEASE PROVIDE INFORMATION THAT THIS SYSTEM IS |
| AN OPTIONAL STAND-BY SYSTEM AND IT DOES NOT SERVE ANY |
| LEGALLY REQUIRED 701, OR EMERGENCY 700 SYSTEMS. |
| ** BASE BUILD OUT PLANS WERE NOT UNDER THE REVIEW OF |
| THIS REVIEWER AND LOADS ARE NOT KNOWN AT THIS TIME. |
| |
| 5) NOTE: PLEASE SEE 702.11. IN ORDER TO MEET EXCEPTIONS |
| IN 225.31-225.39 THE DISCONNECTING MEANS AT GENERATOR |
| MUST BE READILY ACCESSIBLE. PLANS APPEAR TO SHOW IT |
| MEETING OTHER EXCEPTION WHICH IS IT MUST BE *WITHIN |
| SITE*. SEE NEC 100. |
| |
| 6) NOTE: PLEASE LABEL MAINS PER 230.2 E |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |