Plan Review Notes
Plan Review Notes For Permit 09090108
Permit Number 09090108
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-13 11:16:57** DENIED **
  
 ** ORIGINAL REVIEW WAS DONE ON 9/24 HOWEVER DID NOT GET
 INTO THE SYSTEM. NOTES ADDED 10/13
  
  
 1) NOTE: PLANS SUBMITTED ARE IN FACT PHOTO-COPIES OF
 SIGNED, DATED AND SEALED ENGINEERED PLANS. MUST CONTAIN
 ORIGINAL SIGNATURE, DATE AND SEAL PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002, FS 471.025
  
 2) NOTE: RISER INDICATES AN INTERLOCK ENCLOSURE OF SOME
 TYPE. PLEASE PROVIDE EQUIPMENT SPECS MEETING MINIMUM
 LISTING PER UL 1081. IT ALSO INDICATES A NOTE #2, FOR
 WHAT STATES TO BE AS A NEW AUTOMATIC TRANSFER SWITCH.
 PLEASE REVISE RISER IF THIS IS INDEED GOING TO BE
 CHANGED OUT.
  
 3) NOTE: NO PANEL SCHEDULE FOR PANEL *E* COULD BE
 LOCATED. PLEASE SUBMIT SO THAT LOADS CAN BE VERIFIED.
 IT IS NOT POSSIBLE TO REVIEW FOR MINIMUM SIZING PER
 702.5, 220 OF THE NEC AT THIS TIME.
  
 4) NOTE: PLEASE PROVIDE INFORMATION THAT THIS SYSTEM IS
 AN OPTIONAL STAND-BY SYSTEM AND IT DOES NOT SERVE ANY
 LEGALLY REQUIRED 701, OR EMERGENCY 700 SYSTEMS.
 ** BASE BUILD OUT PLANS WERE NOT UNDER THE REVIEW OF
 THIS REVIEWER AND LOADS ARE NOT KNOWN AT THIS TIME.
  
 5) NOTE: PLEASE SEE 702.11. IN ORDER TO MEET EXCEPTIONS
 IN 225.31-225.39 THE DISCONNECTING MEANS AT GENERATOR
 MUST BE READILY ACCESSIBLE. PLANS APPEAR TO SHOW IT
 MEETING OTHER EXCEPTION WHICH IS IT MUST BE *WITHIN
 SITE*. SEE NEC 100.
  
 6) NOTE: PLEASE LABEL MAINS PER 230.2 E
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  