Notes |
Date |
Text |
2009-09-17 09:52:36 | | | ** DENIED PLANS ** | | | | | | 1) NOTE: PLEASE SEE FBC R313.1. PLEASE SHOW A LAYOUT | | ALL EXISTING OR NEW SMOKE ALARMS MEETING CURRENT | | NFPA-72 11.8.3, 11.5.1. MUST BE HARDWIRED WITH BATTERY | | BACK UP. MUST BE INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | AND AT LEAST ONE ON FIRST FLOOR LEADING TO FLOOR ABOVE. | | PLEASE ALSO SEE FS 553.885 AS A CARBON MONOXIDE | | DETECTOR IS REQUIRED FOR HOME WITH THE NEW GAS | | APPLIANCES. | | | | 2) NOTE: PLANS DO NOT INDICATE ANY CIRCUITS FOR NEW AND | | EXISTING REQUIRED DEDICATED CIRCUITS IN KITCHEN | | REMODEL. | | PLEASE SUBMIT A PANEL SCHEDULE SHOWING THE MINIMUM | | CIRCUITS PER 210.52B1, 210.11C1, 220.52 | | PLEASE BE SURE TO INCLUDE MINIMUM CONDUCTORS AND OVER | | CURRENT PROTECTION. | | PLEASE SEE 240.4,310.16 AND 408.4 FOR CONDUCTORS, | | SIZING OF BREAKERS AND PANEL SCHEDULE. | | | | 3) NOTE: PLANS STATE COMPLIANCE WITH NEC. HOWEVER THE | | EDITION OF THE PERMITTED SCOPE OF WORK IS UNDER THE | | 2005 NEC. ( NFPA-70) | | | | | | | | | | ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY | | COMMENTS. | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|