Plan Review Notes
Plan Review Notes For Permit 09090049
Permit Number 09090049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-09-08 15:03:14*****DENIED*****
  
  
 1. THE ACTUAL SITE ADDRESS SHALL BE LISTED IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET, HYDRAULIC
 CALCULATIONS, AND/OR ANY OTHER INFORMATION PERTINENT TO
 THIS PROJECT. IF NEW RESULTS ARE REQUIRED, CONTACT THE
 BUREAU OF FIRE PREVENTION AT 561-804-4724.
  
 2. THE FLOW TEST RESULTS AND HYDRAULIC CALCULATIONS
 SHALL BE BASED ON INFORMATION TAKEN NOT GREATER THAN
 ONE YEAR FROM THE DATED OF PERMIT APPLICATION.
  
 3. THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED
 WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC
 SUPERVISION.
  
 4. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 PROVIDED WITH KNOX LOCKING DEVICES. FOR AN APPLICATION,
 CONTACT THE BUREAU OF FIRE PREVENTION AT 561-804-4724.
  
 5. PROVIDE NOTICE OF COMMENCEMENT OF WHICH THIS SCOPE
 OF WORK IS BEING CONDUCTED. IF THIS SCOPE OF WORK IS
 TIED TO THE MASTER PERMIT, INCLUDE THE MASTER PERMIT
 NUMBER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722