Plan Review Notes For Permit 09090049 |
Permit Number |
09090049 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-08 15:03:14 | *****DENIED***** | | | | | | 1. THE ACTUAL SITE ADDRESS SHALL BE LISTED IN THE TITLE | | BLOCK OF EACH SUBMITTED PLAN SHEET, HYDRAULIC | | CALCULATIONS, AND/OR ANY OTHER INFORMATION PERTINENT TO | | THIS PROJECT. IF NEW RESULTS ARE REQUIRED, CONTACT THE | | BUREAU OF FIRE PREVENTION AT 561-804-4724. | | | | 2. THE FLOW TEST RESULTS AND HYDRAULIC CALCULATIONS | | SHALL BE BASED ON INFORMATION TAKEN NOT GREATER THAN | | ONE YEAR FROM THE DATED OF PERMIT APPLICATION. | | | | 3. THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED | | WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC | | SUPERVISION. | | | | 4. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE | | PROVIDED WITH KNOX LOCKING DEVICES. FOR AN APPLICATION, | | CONTACT THE BUREAU OF FIRE PREVENTION AT 561-804-4724. | | | | 5. PROVIDE NOTICE OF COMMENCEMENT OF WHICH THIS SCOPE | | OF WORK IS BEING CONDUCTED. IF THIS SCOPE OF WORK IS | | TIED TO THE MASTER PERMIT, INCLUDE THE MASTER PERMIT | | NUMBER. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|