Plan Review Notes For Permit 09080790 |
Permit Number |
09080790 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-02 11:00:47 | ****PROVISO**** | | REVISION REQUIRED BEFORE FIRST INSPECTION | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | A PHOTOGRAPH OF A NON IMPACT WINDOW LABEL WAS | | SUBMITTED. SUBMIT THE FOLLOWING DOCUMENTS AS A | | REVISION: | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | FAC9B72. | | | | 2. IMPACT PROTECTION REQUIRED. EITHER SUBMIT PRODUCT | | APPROVAL AND INSTALLATION SCHEDULE FOR SHUTTERS OR | | SUBMIT CALCULATIONS TO SHOW THAT YOU HAVE REPLACED LESS | | THAN 25% OF THE AGGREGATE GLAZED AREA. FBC EB 606.4. | | | | 3. CLARIFY SCOPE OF WORK. IT APPEARS THAT A WINDOW IS | | TO BE REPLACED. APPLICATION STATES "REPAIR JALOUSY | | WINDOW." IF YOU ARE PERFORMING A REPAIR RATHER THAN A | | REPLACEMENT, PLEASE PROVIDE A STRUCTURAL DETAIL. FBC | | R301. | | | | | | |
|