2009-10-28 14:27:01 | ****PASSED W/REDLINE**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. FROM PREVIOUS TWO COMMENT LISTS, SHEATHING NAILING |
| DOES NOT COMPLY WITH FBC R803.2.3.1, SHEET 2, VARIOUS |
| DETAILS. ZONE 3 REQUIRES 4" AT EDGES, PLAN SPECIFIES |
| 6". THIS IS PRESCRIPTIVE IN THE CODE AND CANNOT BE |
| REDUCED. |
| |
| THE DETAILS ON SHEET 2 SPECIFY 30# FELT; THE PRODUCT |
| APPROVAL SUBMITTED DOES NOT ALLOW 30#. PLEASE EITHER |
| REMOVE FROM THE DETAIL OR REVISE SO THAT IT IS |
| CONSISTENT WITH OTHER DETAILS. |
| |
| PLANS HAVE BEEN REDLINED; THE NON CODE COMPLIANT DETAIL |
| HAS BEEN REMOVED. 4"/6" ROOF SHEATHING REQUIRED |
| |
| 2. ROOF PERMIT REQUIRED. FOR A ROOF PERMIT, ENHANCED |
| FASTENING CALCULATIONS REQUIRED PER NOA 08-0221.11, SEE |
| GENERAL LIMITATION #7. THIS MAY BE SUBMITTED SEPARATELY |
| WITH THE ROOF PERMIT APPLICATION. APPROVED ASSEMBLY |
| MUST BE SELECTED AND ENHANCED FASTENING PATTERN |
| SUBMITTED PRIOR TO ROOF PERMIT ISSUANCE. |
| |
| REGARDING THE ROOF DOCUMENTS SUBMITTED: |
| |
| A. ENGINEERING SPECIFIES EXPOSURE B. |
| B. THE NOA SUBMITTED IS FOR "RECOVER DECKS." THIS IS |
| FOR RECOVER APPLICATION, NOT NEW CONSTRUCTION. SUBMIT |
| THE APPROPRIATE NOA. |
| C. AN APPROVED ASSEMBLY MUST BE SELECTED. IT IS NOT |
| CLEAR HOW THE ENGINEER HAS DETERMINED ROOF FASTENER |
| SPACING, MUST DO CALCULATIONS IN ACCORDANCE WITH |
| RAS117. IT APPEARS THAT HE HAS ROUNDED UP, FROM 5.9" TO |
| 6", BUT SEE RAS117 WHICH SPECIFICALLY STATES THAT |
| FASTENING MUST BE ROUNDED DOWN TO THE NEAREST INCH. |
| |
| |
| |