2009-09-14 16:26:46 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. THIS PROPERTY IS LOCATED IN EXPOSURE C, SEE |
| ASCE7-05. EITHER REVISE EXPOSURE AND DESIGN OR PROVIDE |
| RATIONALE FOR EXPOSURE B. FBC R301 |
| |
| 2. PLEASE EXPLAIN DESIGN PRESSURES; FOR INSTANCE, ROOF |
| ZONE 3, 10SF, -68.1 PSF. FBC R301 |
| |
| 3. WIND DESIGN INFORMATION, REFERENCE TO 3 SECOND |
| "BURST," PLEASE CLARIFY, DO YOU MEAN "GUST?" SEE |
| FBC1609, FBC R301, ASCE7-05. |
| |
| 4. SHEATHING NAILING DOES NOT COMPLY WITH FBC |
| R803.2.3.1, SHEET 2, VARIOUS DETAILS. |
| |
| 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR NOA |
| REQUIRED FOR HARDIBOARD SIDING. |
| |
| 6. ROOF PERMIT REQUIRED. FOR A ROOF PERMIT, ENHANCED |
| FASTENING CALCULATIONS REQUIRED PER NOA 08-0221.11, SEE |
| GENERAL LIMITATION #7. THIS MAY BE SUBMITTED SEPARATELY |
| WITH THE ROOF PERMIT APPLICATION. APPROVED ASSEMBLY |
| MUST BE SELECTED AND ENHANCED FASTENING PATTERN |
| SUBMITTED PRIOR TO ROOF PERMIT ISSUANCE. |
| |
| 7. ADDITIONAL FEES DUE (VALUATION ADJUSTMENT, ICC |
| TABLE, TYPE V, UTILITY, $37.87/SF). PLEASE PAY PRIOR TO |
| RESUBMITTAL (CAN BE PAID ONLINE). |
| |