Plan Review Notes
Plan Review Notes For Permit 09080726
Permit Number 09080726
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-14 09:20:32 
  
 ** DENIED PLANS **
  
  
 1) NOTE: COPIES OF SIGNED, DATED AND SEALED PLANS DONE
 BY AN ENGINEER IS NOT PERMITTED. PLEASE SEE FS 471.025,
 FAC 61G15-23.002. PLANS MUST BE DONE BY DESIGN
 PROFESSIONAL MEETING 471, OR 471.003 EXCEPTIONS. THIS
 EXCEPTION MAY BE A LICENSED CONTRACTOR UNDER FS 489.
 PLEASE RE-DRAW PLANS, PRINT NAME AND SIGN.
  
 ** PLANS SHOULD ONLY INDICATE THE SCOPE OF WORK BEING
 APPLIED FOR UNDER PERMIT APPLICATION.
  
 2) NOTE: THERE IS NO CODE DESIGN INFORMATION ON PLANS.
 THE STATE IS CURRENTLY UNDER THE 2005 NFPA-70 AND 2006
 NFPA-101.
 THERE IS NO INFORMATION ON PLANS FOR ACCESS CONTROL
 SYSTEM. NO INFORMATION ON FAIL SAFE OPERATION OF SYSTEM
 WHICH SHALL NO IMPEDE EGRESS UNDER NORMAL OR EMERGENCY
 CONDITIONS.
 PLEASE SEE NFPA-101 CHAPTER 7. PLEASE SEE 7.2, 7.2.1.5,
 7.2.1.6.2 ETC.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  