2009-08-31 15:50:43ELECTRICAL PLAN REVIEW
 PERMIT: 09080664
 ADD: 1432 8TH ST
 CONT: GLADES ROOFING LLC
 TEL: (561)996-5254
  
 2005 NEC
 1ST REVIEW
 ACTION: PROVISO
  
 1) E1- NEW BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE
 COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. PLEASE PROVIDE REVISION INDICATING
 COMPLIANCE BEFORE INSPECTION.
  
 2) PLANS INDICATE NEW KITCHEN CABINETRY AND NEW GFIC
 OUTLET (E3), PLEASE PROVIDE COMPLIANCE WITH
 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).PLEASE
 PROVIDE REVISION INDICATING COMPLIANCE BEFORE
 INSPECTION .
  
 3) E2- INSTALL A NEW DRYER OUTLET, 220.54 ELECTRIC
 CLOTHES DRYERS . DWELLING UNIT(S) THE LOAD FOR
 HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A DWELLING UNIT(S)
 SHALL BE EITHER 5000 WATTS (VOLT-AMPERES) OR THE
 NAMEPLATE RATING, WHICHEVER IS LARGER, FOR EACH DRYER
 SERVED. THE USE OF THE DEMAND FACTORS IN TABLE 220.54
 SHALL BE PERMITTED. WHERE TWO OR MORE SINGLE-PHASE
 DRYERS ARE SUPPLIED BY A 3-PHASE, 4-WIRE FEEDER OR
 SERVICE, THE TOTAL LOAD SHALL BE CALCULATED ON THE
 BASIS OF TWICE THE MAXIMUM NUMBER CONNECTED BETWEEN ANY
 TWO PHASES. TABLE 220.54 1 DRYER 100% DEMAND FACTOR.
  
 PLEASE PROVIDE LOAD CALCULATIONS PER 220. I-IV PLEASE
 PROVIDE BEFORE INSPECTION.
  
  
 JIM WITMER C. B. O.
 SFP-100
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved