2010-01-15 11:38:59 | |
| ** DENIED * |
| |
| ** SOME ITEMS FROM PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED. |
| THERE ARE SEVERAL NEW COMMENTS BASED ON REVISED PLANS |
| SUBMITTED. THE INFORMATION ON PREVIOUS PLANS WAS NOT |
| THE SAME AS THE PLANS NOW SUBMITTED. NEW COMMENTS ARE |
| BASED ON CHANGES NOW ABLE TO BE REVIEWED. |
| |
| 1) NOTE: THIS IS NOTED FOR INFORMATION. SEE COMMENTS |
| FROM OTHER TRADES. SHEET A1.01 IS NOT SIGNED, DATED OR |
| SEALED IN EITHER SET SUBMITTED. THIS IS REQUIRED UNDER |
| FS 481.221. THE ARCHITECT OF RECORD MAY PERSONALLY |
| APPEAR TO SIGN AND SEAL PLANS. A TIME SHOULD BE SET UP |
| WITH STAFF. THIS SHOULD BE NOTED BY OTHER TRADES. |
| |
| 2 ) NOTE: COVER SHEET HAS A CONFLICT IN CODES. ONE ARE |
| INDICATES A 2007 NEC AND THE OTHER 2005. THIS CAN BE |
| RELINED AS THERE WAS NO 2007 CODE. ALL APPLICATIONS FOR |
| PERMIT BEFORE OCTOBER 1ST, 2009 AND AFTER DECEMBER 8TH, |
| 2006 ARE UNDER THE 2005 NEC. |
| NO NFPA-101 LISTED. THIS SHOULD BE 2006 AS NOTED ON |
| PREVIOUS REVIEW. |
| |
| 3) NOTE: THE NEWLY SUBMITTED LIGHTING PERFORMANCE |
| CALCULATIONS NOW SUBMITTED FOR NEW INTERIOR AND |
| EXTERIOR LIGHTING. HOWEVER PLEASE SEE PLANS AS THEY |
| INDICATE THE 2004 FLORIDA BUILDING CODE WITH 2006 |
| SUPPLEMENTS. |
| AFTER MARCH 1ST 2009, THE LIGHTING PERFORMANCE |
| CALCULATIONS ARE REQUIRED TO BE DONE PER 13-415.AB.5 |
| FOR INTERIOR AND 13-415.AB.2.2 FOR EXTERIOR UNDER THE |
| 2007 FBC W/ 2009 SUPPLEMENTS. THERE WERE SUBSTANTIAL |
| CHANGES MADE TO CHAPTER 13, IN FACT THE ENTIRE CHAPTER |
| WAS REVISED. |
| A FIXTURE SCHEDULE WAS NOT SUBMITTED THEREFORE LIGHTING |
| ON PLANS AND CALCULATIONS CAN NOT BE VERIFIED. PLEASE |
| SUBMIT. ( IT CAN ALWAYS BE REVISED AT A LATER DATE IF |
| FIXTURES CHANGE) |
| ** THE LIGHTING SHOWN ON ARCHITECTURAL PLANS FOR WALLS |
| IS MORE THAN THE LIGHTING SHOWN ON THE ELECTRICAL |
| PLANS. ( SCONCES AS ONE EXAMPLE) |
| |
| 4) NOTE: THE NEWLY SUBMITTED LIGHTING PLANS DOES NOT |
| INDICATE LIGHTING CONTROL DETAIL. HOW WILL OCCUPANCY |
| SENSORS BE USED TO MEET FBC 13-415.AB.1.1,.1.2 AND |
| .1.3. LINE VOLTAGE? LOW VOLTAGE? THE SYMBOL LEGEND ONLY |
| INDICATES AN OCCUPANCY SENSOR. |
| THERE IS A SWITCH AT THE REAR DOOR FOR KITCHEN LIGHTING |
| AND ALSO CEILING INDICATES AN OC SENSOR HOWEVER IT IS |
| UNCLEAR HOW THIS WILL BE DONE. THERE ARE SEVERAL WAYS |
| OF INSTALLATION HOWEVER WITHOUT DETAILS WHICH CAN BE |
| TYPICAL IT IS UNCLEAR AT THIS TIME. SEVERAL LIGHTING |
| MANUFACTURE CONTAIN TYPICAL WIRING DETAILS ON THEIR |
| WEBSITE WHICH CAN BE USED. |
| STANDARD SINGLE POLE SWITCHES ARE NOT ACCEPTABLE AS |
| THERE ARE SOME SHOWN ON PLANS. PLEASE ALSO SEE .1.3 OF |
| THE4 SECTION NOTED AS SEPARATE CONTROLS REQUIRED. |
| EXTERIOR LIGHTING DOES INDICATE A PC FOR PHOTO-CELL. |
| |
| 5) NOTE: A COMPLETELY NEW SERVICE RISER WAS SUBMITTED |
| AND THERE ARE COMMENTS BELOW. THERE IS ITEMS INDICATED |
| ON RISER WHICH ARE NOT CLEAR. |
| |
| A) SERVICE SIZE SHOWN FEEDING GUTTER TO PANEL *A* AND |
| *B* IS SHOWN ON PLANS AS A 200AMP METER/MAIN COMBO. HOW |
| IS THIS POSSIBLE WHEN THE LOAD ON THE CALCULATIONS FAR |
| EXCEED THE RATING OF THIS SERVICE EQUIPMENT? |
| ALL SERVICES SERVICE CONDUCTORS ARE TO BE RATED TO THE |
| SIZE OF THE SERVICE PROVIDED AND THE LOAD SERVED. |
| 230.70,230.70,230.90,230.76,230.79 ETC. |
| |
| B) THE RISER INDICATES SEVERAL DIFFERENT LABELS TO |
| EXISTING CONDUCTORS ETC HOWEVER IT IS UNCLEAR WHICH |
| CONDUCTORS IS FOR WHICH SERVICE, RISER, AND CONDUCTOR. |
| SEE RISER, JUST ABOVE THE METER MAIN COMBO THERE IS A |
| NOTE FOR EXISTING CONDUCTORS FOR 3-3/0 AND 1-#6. WHAT |
| IS THIS FOR? THE SERVICE EQUIPMENT JUST TO THE LEFT |
| ALREADY INDICATES CONDUCTORS. |
| IF THIS IS FOR RISER TO 200AMP METER/MAIN COMBO THE |
| CONDUCTORS ARE NOT SUFFICIENT FOR SERVICE SIZE. |
| IF THIS IS FOR RISER TO 200AMP METER/MAIN COMBO THE |
| RISER INDICATES AND * EQUIPMENT GROUNDING CONDUCTOR* |
| BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| PERMITTED. PLEASE SEE 250.6 AND 250.24 AS THIS WOULD |
| PARALLEL THE NEUTRAL CREATING OBJECTIONABLE CURRENT. |
| |
| C) THE RISER JUST BELOW THE SERVICE METER/MAIN COMBO |
| INDICATES EXISTING #2 AND EXISTING 1/0 HOWEVER THESE |
| ARE GOING TO ANYTHING. WHAT ARE THESE FOR? |
| |
| D) THE LOAD CALCULATIONS FOR PANEL *B* INDICATES LOAD |
| AT 196.4 AMPS AND NOTES THAT A 225AMP SERVICE IS |
| SUFFICIENT. THIS IS NOT POSSIBLE WHEN THE MAIN FEEDING |
| THIS SAME 225AMP MLO IS SHOWN ON RISER TO BE 200AMPS. |
| THE SERVICE IS 200AMPS WHICH PLACES THIS LOAD OF 196 |
| AMP VERY CLOSE TO THE MAXIMUM RATING OF A 200AMP |
| BREAKER. |
| 240.4, 230.76, 230.79, 230.70, 230.71, 215.5, ETC |
| |
| E) THE RISER DOES ALSO LIST 350MCM FOR SOMETHING |
| HOWEVER EVEN IF THESE ARE THE SIZE CONDUCTORS IN |
| GUTTER, THE SERVICE IS ONLY 200AMPS. THE SERVICE WILL |
| BE REQUIRED TO BE UPGRADED. THE LOADS ALONE ARE 313 |
| PLUS AMPS AND 350MCM IS RATED FOR 310. THE CONDUCTORS |
| ARE NOT SUFFICIENT.310.16, 110.14 |
| |
| F) THE LOADS ON THE SERVICE ARE TO BE REVISED. WHERE |
| ARE THE LOADS ON PANEL *A* FOR EXTERIOR LIGHTING? ALL |
| CONTINUOUS LOADS INCLUDING LOADS ON EXTERIOR LIGHTING |
| IS TO BE SHOWN AT 125%. |
| THE LOAD FOR LIGHTING IS SHOWN AT 2VA PER SQ FT. IT IS |
| NOT PERMITTED TO USE THE 2VA PER SQ FT IF THE ACTUAL |
| LIGHTING LOAD IS HIGHER. THE LIGHTING FIXTURE LEGEND |
| WAS SUBMITTED SO THIS CAN NOT BE CONFIRMED WHICH LOAD |
| IS GREATER. |
| NO TRACK LIGHTING LOADS ARE SHOWN? |
| NO SHOW WINDOW LOADS ARE SHOWN? IF THERE IS WINDOW AREA |
| ABOVE DOORS RECEPTACLES WILL BE REQUIRED. THE INTENT OF |
| 210.62 IS THAT QUITE OFTEN SIGNS ARE HUNG IN THESE |
| AREAS. |
| THE LOAD SHOWN FOR RECEPTACLES IS LESS THAN WHAT IS |
| ACTUALLY ON PLANS. PLEASE SEE SECTIONS GIVEN FOR THE |
| 180VA PER RECEPTACLE. THE CALCULATIONS INDICATE 10, |
| HOWEVER THERE ARE MORE CONVENIENCE OUTLETS ON PLANS. |
| PLEASE SEE 220.12, 220.14, 220.42, AND 220.43. ETC |
| |
| 6) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20AMP, 120V |
| RECEPTACLES IN KITCHEN AREAS SHALL BE GFI/GFI |
| PROTECTED. THIS IS REQUIRED WHETHER OR THESE ARE |
| FEEDING COUNTER SPACE LOCATIONS. |
| THERE IS NO GFI PROTECTION ON PANEL SCHEDULES OR ON |
| PLANS. |
| THIS INCLUDES BAR AREA RECEPTACLES. 210.8B3 |
| |
| 7) NOTE: PLEASE SEE 408.4 REVISED UNDER THE 2005 CODE. |
| IT IS NOT PERMITTED TO USE *GENERAL LIGHTING OR GENERAL |
| RECCEPTACLES * TO DESCRIBE CIRCUITING. THESE ARE |
| REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| THEY FEED. THIS MAY BE DONE PART OF A PROVISO TO BE |
| REVISED AND SUBMITTED BEFORE FINAL. SEE CODE COMMENTARY |
| IN THE HANDBOOK WHICH PROVIDES INFORMATION. RECORD |
| PLANS NEED TO CONTAIN SPECIFIC INFORMATION/DETAIL. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |