Plan Review Notes
Plan Review Notes For Permit 09080604
Permit Number 09080604
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-18 20:01:00 
 ** DENIED **
  
 ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS
 SUBMITTED.
  
 1) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 RELEVANT CODES.
 2006 NFPA-101
 2005 NFPA-70
 2007 FBC WITH 2009 REVISIONS.
  
 ** PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL PLANS.
 THE FOLLOWING IS NOTED AS THERE ARE ITEMS NOT YET
 SUBMITTED.
  
 2) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING
 CONTROLS.
  
 3) NOTE: PLEASE PROVIDE NEW AND EXISTING LIGHTING
 LOCATIONS. NEED TO VERIFY LIGHTING FOR EGRESS
 REQUIREMENTS OF LOCATION. NEW AREAS APPEAR TO MEET
 MINIMUM LEVELS UNDER BATTERY BACK UP PER NFPA- 101
 7.8.1.3,7.9.1.2,7.9.2.2, FBC 1006.1.2
 PLEASE PROVIDE LIGHTING NEW OR EXISTING FOR BATHROOMS.
  
 4) NOTE: PLEASE SURE TO SHOW CIRCUITING ON PLANS FOR
 NEW. PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHTS.
  
 5) NOTE: PLANS STATE NEW SIGN. PLEASE SEE 600.5 FOR
 REQUIRED DEDICATED SIGN CIRCUIT TO BE SHOWN ALONG WITH
 LOAD PER SAME SECTION. MINIMUM OF 1200VA REQUIRED.
  
 6) NOTE: PLEASE PROVIDE PANEL SCHEDULE OR NOTE NEW
 CIRCUITS. 408.4.
  
 7) NOTE: PLEASE PROVIDE THE LATEST ELECTRICAL RISER FOR
 RECENT SERVICE CHANGE DONE ON PLANS.
 215.5,230.2, 240.4,310.16, 230.70.
  
 ** SOME OF THE ABOVE ITEMS COULD BE SET UP AS A
 PROVISO. PLEASE CALL TO GO OVER.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  