Plan Review Notes
Plan Review Notes For Permit 09080604
Permit Number 09080604
Review Stop B
Sequence Number 1
Notes
Date Text
2009-09-09 11:45:55BUILDING PLAN REVIEW
 PERMIT: 09080604
 ADD: 519 CLEMATIS ST.
 CONT: SEC
 TEL: (561)797-6007
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 09-09-09
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLANS ARE DEFICIENT IN THE FOLLOWING ITEMS, 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS:
 106.3.5(2) OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED.
  
 (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 (4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS TABLE 601
  
 (5) FIRE SUPPRESSION SYSTEMS, ARE THER FIRE SPRINKLERS?
 903
 PLANS DO NOT PROVIDE FIRE EXTINGUISHER LOCATIONS 906.1
  
 (6) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD TABLE 1004.1.1
 MEANS OF EGRESS / EXIT ACCESS 1015/ AISLE ACCESSWAYS
 1014.4.3.3
  
 (8) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 803.1/ TABLE 803.5
 SANITATION 1210.2
  
 (9) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE BOTH FOR THE INTERIOR AND PATIO DECK
 RESTROOMS
  
 3) SHEET A.02 INDICATESA STALL WITHIN THE MENS
 RESTROOM, THE NEW WORK SHEET A.03 INDICATES THE STALL
 NOW DOES NOT HAVE A TURNING RADIUS WITHIN THE STALL,
 PLEASE REVIEW 11-4.1.6 ACCESSIBLE BUILDINGS-
 ALTERATIONS (1)
 A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES OR
 HAS THE EFFECT OF DECREASING ACCESSIBILITY OR USABILITY
 OF A BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR
 NEW CONSTRUCTION AT THE TIME OF ALTERATION.
  
 (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
  
 (C) IF ALTERATIONS OF SINGLE ELEMENTS, WHEN CONSIDERED
 TOGETHER, AMOUNT TO AN ALTERATION OF A ROOM OR SPACE IN
 A BUILDING OR FACILITY, THE ENTIRE SPACE SHALL BE MADE
 ACCESSIBLE.
  
 4) PLEASE ALSO PROVIDE A FLOOR PLAN INDICATING
 COMPLIANCE WITH :
 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS
 SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH
 THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18). ETWEEN THE SMOKING
 AND NONSMOKING AREAS. IN NEW CONSTRUCTION, AND WHERE
 PRACTICABLE IN ALTERATIONS, ACCESSIBLE FIXED TABLES (OR
 COUNTERS) SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR
 FACILITY.
  
 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING
 AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS
 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED
 IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL
 BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36
 INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES
 OR BETWEEN A WALL AND THE TABLE EDGES.
  
 11-5.4 DINING AREAS. IN NEW CONSTRUCTION, ALL DINING
 AREAS, INCLUDING RAISED OR SUNKEN DINING AREAS,
 LOGGIAS, AND OUTDOOR SEATING AREAS, SHALL BE
 ACCESSIBLE. IN ALTERATIONS, ACCESSIBILITY TO RAISED OR
 SUNKEN DINING AREAS, OR TO ALL PARTS OF OUTDOOR SEATING
 AREAS IS NOT REQUIRED PROVIDED THAT THE SAME SERVICES
 AND DECOR ARE PROVIDED IN AN ACCESSIBLE SPACE USABLE BY
 THE GENERAL PUBLIC AND ARE NOT RESTRICTED TO USE BY
 PEOPLE WITH DISABILITIES.
  
 5) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE A
 120MPH / 3SECOND GUST, PLEASE REVIEW FIGURE 1609 THE
 CITY OF WEST PALM BEACH IS ENTIRELY LOCATED WITHIN A
 140 MPH WIND ZONE, PLEASE UPDATE PLANS.
  
 6) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE FLOOR
 LOADS OF 40 PSF LIVE LOADS PLEASE REVIEW TABLE 1607.1
 DINING ROOMS & RESTARAUNTS OF 100 PSF, OR ASSEMBLY WITH
 MOVABLE SEATS 100 PSF.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE OF
 FLOOR SYSTEM, PLANS APPEAR TO INDICATE A FLOOR TRUSS
 SYTEM?
  
 7) BOTH A.05 & S1 BOTH INDICATE A NEW OPENING ON THE
 SIDE OF THE BUILDING WITH A PAIR OF GLAZED OPENINGS &
 TWO SIDELIGHTS. THE PRODUCT SUBMITTED FL 10356-R1 IS
 ONLY FOR A PAIR OF DOORS NON-IMPACT. MISSING PRODUCT
 APPROVALS ARE:
 7A) FIXED OR STOREFRONT WINDOWS/ SIDELIGHTS
 7B) VERTICAL MULLION
 7C ) STORM SHUTTTERS/ PANELS
  
 8) STORM SHUTTERS PLEASE PROIDE THE FOLLOWING: FL BLD
 CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & EXIST
 BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  