2009-08-31 07:11:52DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. THE GREASE/SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN NOR MEET CODE REQUIREMENTS. THE CLEANOUT
 INDICATED BY THE INLET OF THE GREASE INTERCEPTOR ON THE
 GREASE/SANITARY RISER DIAGRAM IS NOT SHOWN ON THE FLOOR
 PLAN. TWO WAY CLEANOUTS ARE REQUIRED ON THE INLET AND
 OUTLET OF EACH GREASE INTERCEPTOR. THE FLOOR DRAIN IN
 THE AREA OF THE WAREWASHER SHALL BE CONNECTED TO THE
 GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTIONS
 106.1.1, 1003.1, 1003.3.1 & UTILITY STANDARDS.
  
 2. THE GREASE INTERCEPTOR SHALL BE APPROVED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT/ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR PHONE NUMBER (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. A WRITTEN OR
 E-MAIL DETERMINATION IS REQUIRED SHOWING APPROVAL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  