2009-08-31 07:11:52 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| |
| 1. THE GREASE/SANITARY RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN NOR MEET CODE REQUIREMENTS. THE CLEANOUT |
| INDICATED BY THE INLET OF THE GREASE INTERCEPTOR ON THE |
| GREASE/SANITARY RISER DIAGRAM IS NOT SHOWN ON THE FLOOR |
| PLAN. TWO WAY CLEANOUTS ARE REQUIRED ON THE INLET AND |
| OUTLET OF EACH GREASE INTERCEPTOR. THE FLOOR DRAIN IN |
| THE AREA OF THE WAREWASHER SHALL BE CONNECTED TO THE |
| GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTIONS |
| 106.1.1, 1003.1, 1003.3.1 & UTILITY STANDARDS. |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE APPROVED BY THE |
| UTILITY DEPT. INDUSTRIAL PRETREATMENT/ENVIRONMENTAL |
| COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY |
| SUPERVISOR PHONE NUMBER (561) 822-2271, FAX (561) |
| 822-2279 OR E-MAIL [email protected]. A WRITTEN OR |
| E-MAIL DETERMINATION IS REQUIRED SHOWING APPROVAL. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |