2009-08-27 19:58:40 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. NO MECHANICAL SCOPE OF WORK SHOWN ON PLANS FOR HVAC |
| SYSTEM IN THE SPACE. ANY WORK IN THIS AREA SHALL BE |
| UNDER SEPARATE PLANS AND PERMIT. |
| |
| 2. PLANS CONTAIN NOA DATA FOR GREASE EXHAUST FAN WITH |
| INSTALLATION INSTRUCTIONS AND WIND RESISTANCE DATA. NO |
| SUCH INFORMATION WAS PROVIDED FOR SUPPLY FAN. PROVIDE |
| SUPPLY FAN WIND RESISTANCE DATA AND INSTALLATION |
| INSTRUCTIONS IN ACCORDANCE WITH FBC-M 301.12. |
| NOTE: FAN SCEDULE STATES "OR EQUAL." ANY CHANGE IN |
| EQUIPMENT WILL REQUIRE ADDITIONAL INFORMATION REGARDIN |
| WIND RESISTANCE. |
| |
| 3. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED |
| TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER |
| COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST |
| FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING |
| APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF |
| OTHER APPROVED METHODS IN ACCORDANCE WITH FBC-M |
| 507.2.1.1. |
| |
| 4. HOOD/FAN SCHEDULES SHOW THE SUPPLY FAN WITH HIGHER |
| CFM THAN EXHAUST FAN. THIS WOULD PREVIENT THE KITCHEN |
| FROM BEING IN A 0.02" WC NEGATIVE PRESSURE AS REQUIRED |
| BY PLAN NOTES AND FBC-B SECTION 13-409.AB.3.5.1. SHOW |
| PROPERLY BALANCES SUPPLY AND EXHAUST. |
| |
| HOOD AND HOOD SUPPRESSION SYSTEMS SHALL BE UNDER |
| SEPARATE PERMITS. |
| |