2009-08-27 19:58:40REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL SCOPE OF WORK SHOWN ON PLANS FOR HVAC
 SYSTEM IN THE SPACE. ANY WORK IN THIS AREA SHALL BE
 UNDER SEPARATE PLANS AND PERMIT.
  
 2. PLANS CONTAIN NOA DATA FOR GREASE EXHAUST FAN WITH
 INSTALLATION INSTRUCTIONS AND WIND RESISTANCE DATA. NO
 SUCH INFORMATION WAS PROVIDED FOR SUPPLY FAN. PROVIDE
 SUPPLY FAN WIND RESISTANCE DATA AND INSTALLATION
 INSTRUCTIONS IN ACCORDANCE WITH FBC-M 301.12.
 NOTE: FAN SCEDULE STATES "OR EQUAL." ANY CHANGE IN
 EQUIPMENT WILL REQUIRE ADDITIONAL INFORMATION REGARDIN
 WIND RESISTANCE.
  
 3. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST
 FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING
 APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF
 OTHER APPROVED METHODS IN ACCORDANCE WITH FBC-M
 507.2.1.1.
  
 4. HOOD/FAN SCHEDULES SHOW THE SUPPLY FAN WITH HIGHER
 CFM THAN EXHAUST FAN. THIS WOULD PREVIENT THE KITCHEN
 FROM BEING IN A 0.02" WC NEGATIVE PRESSURE AS REQUIRED
 BY PLAN NOTES AND FBC-B SECTION 13-409.AB.3.5.1. SHOW
 PROPERLY BALANCES SUPPLY AND EXHAUST.
  
 HOOD AND HOOD SUPPRESSION SYSTEMS SHALL BE UNDER
 SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]