Plan Review Notes For Permit 09080601 |
Permit Number |
09080601 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-31 07:23:42 | DENIED | | REFERENCE: | | FBC-2007 FUEL GAS | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS | | PERMIT: | | | | 1. TYPE OF GAS, (LP OR NATURAL). | | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE | | SEC. G2413.2. -- ONLY ONE COPY SUBMITTED. MINIMUM 2 | | COPIES OF SPECIFICATIONS REQUIRED. (SECTION 106.1). | | | | 3. PLEASE INDICATE THE SIZE OF EACH SHUT OFF VALVE. (1" | | REQUIRED FOR W/H, MIN 1/2" REQUIRED FOR CHAR GRILLE, | | 1-1/4" REQUIRED FOR RANGE & 3/4" REQUIRED FOR FRYER). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|