Plan Review Notes
Plan Review Notes For Permit 09080601
Permit Number 09080601
Review Stop G
Sequence Number 1
Notes
Date Text
2009-08-31 07:23:42DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. TYPE OF GAS, (LP OR NATURAL).
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2. -- ONLY ONE COPY SUBMITTED. MINIMUM 2
 COPIES OF SPECIFICATIONS REQUIRED. (SECTION 106.1).
  
 3. PLEASE INDICATE THE SIZE OF EACH SHUT OFF VALVE. (1"
 REQUIRED FOR W/H, MIN 1/2" REQUIRED FOR CHAR GRILLE,
 1-1/4" REQUIRED FOR RANGE & 3/4" REQUIRED FOR FRYER).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  