Plan Review Notes
Plan Review Notes For Permit 09080601
Permit Number 09080601
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-27 08:00:20BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 PROVISOS:
  
 1) PROVIDE COMPLIANCE WITH : [F] 904.11.1 MANUAL SYSTEM
 OPERATION. A MANUAL ACTUATION DEVICE SHALL BE LOCATED
 AT OR NEAR A MEANS OF EGRESS FROM THE COOKING AREA A
 MINIMUM OF 10 FEET (3048 MM) AND A MAXIMUM OF 20 FEET
 (6096 MM) FROM THE KITCHEN EXHAUST SYSTEM. THE MANUAL
 ACTUATION DEVICE SHALL BE INSTALLED NOT MORE THAN 48
 INCHES (1200 MM) OR LESS THAN 42 INCHES (1067 MM) ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED. THE MANUAL ACTUATION SHALL REQUIRE A MAXIMUM
 FORCE OF 40 POUNDS (178 N) AND A MAXIMUM MOVEMENT OF 14
 INCHES (356 MM) TO ACTUATE THE FIRE SUPPRESSION SYSTEM.
  
 2) PROVIDE PRODUCT APPROVALS AT TIME OF INSPECTION FOR
 SUPPLY, EXHAUST FANS AND ROOF CURBING.
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  