2009-08-31 18:33:59 | APPROVED WITH PROVISO: | | 1. MUST SUBMIT REVISED MECHANICAL PLAN, FOR REVIEW AND | | APPROVAL, WHICH INDICATES THE SIZE AND TYPE OF REQUIRED | | FIRE DAMPERS TO BE INSTALLED IN BOTH SUPPLY AND RETURN | | AIR DUCTS WHICH PENETRATE THE FIRE RATED WALLS | | INDICATED ON THE PLANS SUBMITTED, PRIOR TO INSTALLATION | | IN THE FIELD. PLEASE INCLUDE FIRE DAMPER SPECIFICATIONS | | AND INSTALLATION DETAILS WHICH HAVE BEEN STAMPED | | "APPROVED AS NOTED" BY THE DESIGN PROFESSIONAL. |
|