2009-08-27 15:09:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENGINEER'S NAME AND LICENSE NUMBER SHALL BE PRINTED
 IN TITLE BLOCK ON M PAGE IN ACCORDANCE WITH FAC RULE
 61G15-23.002
  
 2. ENERGY CALCULATIONS SHALL BE CERTIFIED, SIGNED AND
 DATED BY THE PREPARER AND OWNER/AGENT IN ACCORDANCE
 WITH FBC-B 13-103.1.1.
  
 3. A SYSTEM SIZING SUMMARY WAS PROVIDED IN LIEU OF FULL
 COOLING/HEATING LOAD CALCULATIONS. THE SUMMARY SHALL BE
 SIGNED AND SEALED BY THE ENGINEER IN ACCORDANCE WITH
 FBC-B 13-607.1.
  
 NOTE: PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 PASSED. REVIEW IS IN FAIL STATUS PENDING COMPLIANCE
 WITH THE ABOVE ADMINISTRATIVE PROVISIONS.
  