Plan Review Notes For Permit 09080470
Permit Number 09080470
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-26 09:21:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED
  
 1} 230.72 GROUPING OF DISCONNECTS
 (A) GENERAL THE TWO TO SIX DISCONNECTS AS PERMITTED IN
 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE
 MARKED TO INDICATE THE LOAD SERVED.***THE LOCATION OF
 THE METERS AND DISCONNECTS SHOWN ON THE PLAN WOULD
 INDICATE 2 SERVICES TO THE SAME BUILDING IN VIOLATION
 OF 230.2
  
 2} 401.4 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  