2009-08-25 11:25:172007 FBC W/2007 REVISIONS
 CHANGE OF OCCUPANCY FROM R2 TO R3
  
 DENIED BY BUILDING
  
 1) SPECIFY THE OCCUPANCY TYPE, TYPE OF CONSTRUCTION AND
 LEVEL OF ALTERATION ON THE PLANS. SEE FBC 302, FBC 602
 AND FBC EXISTING BUILDING 401.4.
  
 2) SPECIFY THE ENTIRE SCOPE OF WORK ON THE PLANS.
  
 3) THE VALUE SPECIFIED FOR THE APPARENT SCOPE OF WORK
 IS LOW. PLEASE REVISE THE VALUE TO INCLUDE THE COSTS OF
 MATERIALS, LABOR, DESIGN, OVERHEAD AND PROFIT FOR ALL
 STRUCTURAL, . CITY AMENDMENTS *FBC 108.3
  
 4) THE STRUCTURE IS LOCATED IN AN A9 FLOOD ZONE. ANY
 NEW EQUIPMENT IS REQUIRED TO BE ABOVE THE ELEVATION OF
 13' 6".
  
 5) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT.
 FBC CHAPTER 13.
  
 6) ON SHEET 3, THE ANSI/UL ONE HOUR WALL DETAIL FOR
 DESIGN NO. U404 IS INCORRECT. THIS DESIGN REQUIRES 20
 GA. STEEL STUDS @ 16" O.C. WITH 3" MINERAL WOOL BATTS.
 PLEASE REVISE. SEE DESIGN NO. U432, WHICH IS FOR ONE
 HOUR NON-BEARING WALLS WITH 20 GA. STEEL STUDS @ 24"
 0.C. AND ANY LISTED GLASS FIBER OR MINERAL WOOL
 INSULATION.
  
 7) THE ONE HOUR FIRE WALL DETAIL ALSO SPECIFIES R-19
 INSULATION IN A NOMINAL 4" WALL. PLEASE REVISE TO
 INSULATION THAT WILL CORRECTLY FIT IN THE WALL.
  
 8) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE OPENING
 PRESSURES, SIZES, SPANS, MOUNT TYPE, ANCHOR TYPE,
 ANCHOR SPACING, EDGE DISTANCE, GLASS SEPARATION, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]