2009-08-25 11:25:17 | 2007 FBC W/2007 REVISIONS |
| CHANGE OF OCCUPANCY FROM R2 TO R3 |
| |
| DENIED BY BUILDING |
| |
| 1) SPECIFY THE OCCUPANCY TYPE, TYPE OF CONSTRUCTION AND |
| LEVEL OF ALTERATION ON THE PLANS. SEE FBC 302, FBC 602 |
| AND FBC EXISTING BUILDING 401.4. |
| |
| 2) SPECIFY THE ENTIRE SCOPE OF WORK ON THE PLANS. |
| |
| 3) THE VALUE SPECIFIED FOR THE APPARENT SCOPE OF WORK |
| IS LOW. PLEASE REVISE THE VALUE TO INCLUDE THE COSTS OF |
| MATERIALS, LABOR, DESIGN, OVERHEAD AND PROFIT FOR ALL |
| STRUCTURAL, . CITY AMENDMENTS *FBC 108.3 |
| |
| 4) THE STRUCTURE IS LOCATED IN AN A9 FLOOD ZONE. ANY |
| NEW EQUIPMENT IS REQUIRED TO BE ABOVE THE ELEVATION OF |
| 13' 6". |
| |
| 5) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT. |
| FBC CHAPTER 13. |
| |
| 6) ON SHEET 3, THE ANSI/UL ONE HOUR WALL DETAIL FOR |
| DESIGN NO. U404 IS INCORRECT. THIS DESIGN REQUIRES 20 |
| GA. STEEL STUDS @ 16" O.C. WITH 3" MINERAL WOOL BATTS. |
| PLEASE REVISE. SEE DESIGN NO. U432, WHICH IS FOR ONE |
| HOUR NON-BEARING WALLS WITH 20 GA. STEEL STUDS @ 24" |
| 0.C. AND ANY LISTED GLASS FIBER OR MINERAL WOOL |
| INSULATION. |
| |
| 7) THE ONE HOUR FIRE WALL DETAIL ALSO SPECIFIES R-19 |
| INSULATION IN A NOMINAL 4" WALL. PLEASE REVISE TO |
| INSULATION THAT WILL CORRECTLY FIT IN THE WALL. |
| |
| 8) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. SPECIFY THE OPENING |
| PRESSURES, SIZES, SPANS, MOUNT TYPE, ANCHOR TYPE, |
| ANCHOR SPACING, EDGE DISTANCE, GLASS SEPARATION, ETC. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |