2009-08-19 16:55:48DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
 1. LI-1 POINT OF CONNECTION DETAIL INDICATES A FEBCO
 805 V DOUBLE CHECK BACKFLOW FOR THE IRRIGATION. THIS IS
 NOT APPROVED. AN RPZB BACKFLOW IS REQUIRED PER TABLE
 608.1.
  